c.de.1
Command Delay 1
Command 1 delay (only in ON / OFF functioning).
-60:00..60:00 mm:ss.
Default
: 00:00.
Negative: delay when turning off output.
Positive: delay when turning on output.
46
c.S.p.1
Command Setpoint Protection 1
Allows or not to modify command setpoint 1 value
FrEE
Modification allowed (
Default
)
Lock
Protected
FR.iN.
Free Initialized. At start, setpoint 1 of command 1 is initialized to the value set on
parameter 51
i.SP.1
(Initial Value Setpoint 1).
48
a.ma.1
Automatic / Manual 1
Enables the automatic/manual selection for command 1
diSab.
Disabled (
Default
)
Enab.
Enabled
En.Sto.
Enabled with memory
49
ini.S.
Initial State
Choose the state of the controller when turning it on. This only works on the RS485 version or by
enabling the Start/Stop from digital input or
SET
button.
Start
Start (
Default
)
stop
Stop
Store.
Stored. State of Start/Stop prior to switching off.
51
i.SP.1
Initial Value Setpoint 1
Determines the initial value (at start) of setpoint 1 of command 1 when
FR.iN.
is selected on
parameter 46
c.S.p.1
(Command Setpoint Protection 1)
-9999..+30000 [digit
] (degrees for temperature sensors).
Default
0.
52÷53
Reserved Parameters - Group C
Reserved parameters - Group C