background image

D200-89-00

2

I56-1332-02

2. Tamper Resistance:

The sensor bases have a tamper-resistant capability. When this capability is enabled, sensors cannot be removed from
the base without the use of a small screwdriver or other similar tool. Refer to the sensor base installation instruction
manual for details in using this capability.

3. After all sensors have been installed, apply power to the control unit.

4. Test the sensor by placing a small magnet against the sensor plastic, as shown in Figure 2. The alarm level should be

recognized in the panel and the LED controlled by communication command from the panel.

5. The reset of the sensor LED is controlled by communication command from the panel.

TESTING

Sensors must be tested after installation and periodic maintenance. The sensor may be tested in the following ways.

A. Test Magnet (Model No. M02-04)

1. Place the magnet against the cover in the magnet test area as shown in Figure 2 to activate the test feature.
2. The LEDs should latch ON within 10 seconds, indicating alarm and annunciating the panel.
3. Reset the detector at the system control panel.

B. Test sensitivity from the control panel.

C. Direct Heat Method (Hair dryer of 1000 – 1500 watts)

1. From the side of the detector, direct the heat toward the sensor. Hold the heat source about  6 inches (15cm) away to

prevent damage to the cover during testing.

NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.

NOTE: Verify that all sensor bases are installed and that the wiring polarity is correct at each base.

WARNING:

Disconnect the power from the loop before installing sensors.

1. Install Sensors:

a. Verify that the sensor type matches the type written on the label in the base.
b. Set the sensor to a desired address and then write the address on the label on the base.
c. Place the sensor into the sensor base.
d. Turn the sensor clockwise until it drops into place.
e. Continue turning the sensor clockwise to lock it in place.

3

2

1

3

2

1

3

2

1

+

-

-

+

U.L. LISTED COMP

A

TIBLE

CONTROL

 P

ANEL

CLASS A OPTIONAL WIRING

REMOTE ANNUNCIATOR

+

-

CAUTION: Do not loop wire under terminal 1 or 2.
Break wire run to provide supervision of connections.

A78-1253-01

Figure 1

Technical Manuals Online! - http://www.tech-man.com

Содержание System Sensor 5251RP

Страница 1: ... the normal condition by code com mand Remote LED annunciator capability is available as an optional accessory Part No RA400Z SPECIFICATIONS Diameter 6 1 inches 155 mm installed in B210LP 4 1 inches 104 mm installed in B501 Height 2 0 inches 51 mm Weight 5 ounces 150 gm Installation Temperatures 4 F to 100 F 20 C to 38 C Operating Humidity Range 10 to 93 Relative Humidity Non condensing Mounting B...

Страница 2: ...cating alarm and annunciating the panel 3 Reset the detector at the system control panel B Test sensitivity from the control panel C Direct Heat Method Hair dryer of 1000 1500 watts 1 From the side of the detector direct the heat toward the sensor Hold the heat source about 6 inches 15cm away to prevent damage to the cover during testing NOTE All wiring must conform to applicable local codes ordin...

Страница 3: ...gure 3 Figure 2 Views showing position of test magnet MAINTENANCE NOTE Before cleaning notify the proper authorities that the system is undergoing maintenance and therefore the system will temporarily be out of service Disable the loop or system undergoing maintenance to prevent unwanted alarms It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors...

Страница 4: ...ed through the local manufacturer s representative Though heat detectors are designed for long life they may fail at any time Any heat detector fire system or any component of that system which fails shall be repaired or replaced immediately Refer to NFPA 72 for application This heat detector is designed to activate and initiate emergency action but will do so only when it is used in conjunction w...