D200-51-00

2

I56-548-06

Figure 1:

2. Tamper-Resistance
      Model  1251  includes  a  tamper-resistant  capability  that

prevents its removal from the bracket without the use of
a  tool.  Refer  to  the  base  manual  for  details  on  making
use of this capability.

3. After all sensors have been installed, apply power to the

system.

4. See Figure 2. Test the sensor by positioning a test mag-

net (M02-24) against the sensor plastic just to the left of
LED1. The alarm level should be recognized at the panel
and  the  LED  controlled  by  communication  command
from the panel.

5. Reset the sensor by communication command from the

panel.

Testing

Detectors  must  be  tested  after  installation  and  following
periodic  maintenance.  However,  before  testing,  notify  the
proper authorities that the smoke detector system is under-
going maintenance and the system will be temporarily out
of service. Disable the zone or system undergoing mainte-
nance to prevent unwanted alarms.

In addition, check to ensure that the LEDs blink. If they do
not, power has been lost to the detector (check the wiring),
or it is defective (return it for repair).

Test the sensors as follows:
A. Test Magnet (Model M02-24 -optional)

1. Test the sensor by positioning the optional test mag-

net against the sensor plastic just to the left of LED1,

as shown in Figure 2.

2. Both LEDs should latch on within 30 seconds, indicat-

ing an alarm and annunciating the panel.

B. Calibrated Sensitivity Test (MOD400R)
    Use the MOD400R Test Module with a digital or analog

voltmeter  to  test  calibrated  detector  sensitivity  as  de-
scribed in the test module manual.

C. Aerosol Generator in accordance with NFPA 72.

The Gemini Model 501 aerosol generator can be used to
test  the  sensor.  Set  the  generator  to  represent  4%/ft to
5%/ft obscuration, following the instructions in the gen-
erator  manual.  Use  a  bowl  shaped  applicator  to  apply
aerosol to the sensor. It should alarm after 30 seconds.