1251 Plug-in Intelligent Ionization

Sensor with Communications

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please read the system wiring and installation manual, I56-
407. This manual includes detailed information on sensor
spacing, placement, zoning, and special applications. Cop-
ies of this manual are available from System Sensor.

General Description

The  Model  1251  intelligent  ionization  sensor  uses  a  state-
of-the-art sensing chamber. This sensor is designed to pro-
vide  open  area  protection  and  is  intended  for  use  with
compatible control panels only.

Two  LEDs  on  each  sensor  light  to  provide  a  local,  visible
sensor  indication.  The  LEDs  can  be  latched  on  by  code
command  from  the control  panel  for  an alarm  indication.
The LEDs can also be unlatched to the normal condition by
code command. Remote LED annunciator capability is also
available as an optional accessory (RA400Z).

Specifications

Operating Voltage Range:

15 to 32 VDC

Max. Avg. Standby Current:

300

µ

A

 

@ 24 VDC (one

 

communication every 5 sec. with LED blink  enabled)

Max.  Alarm Current (LED on):

6.5 mA @ 24  VDC

Operating Humidity Range:

10% to 93% Relative Humidity, noncondensing

Operating Temperature Range:

0° to 49°C (32° to 120°F)

Height:

1.7 inches (43 mm) installed in B210LP Base

Diameter:

6.2 inches (155 mm) installed in B210LP Base
4.1 inches (104 mm) installed in B501 Base

Weight:

3.6 oz. (102 g)

Wiring Guide

Refer to the installation instructions for the plug-in base be-
ing  used.  As  indicated  in  Figure  1,  terminals  for  power,
ground, and the optional RA400Z Remote Annunciator are
included in the base. Base Models B210LP (shown in Figure
1) and B501 are electrically identical.

NOTE:

All  wiring  must  conform  to  all  applicable  codes,
ordinances, and regulations.

NOTE:

Verify  that  all  sensor  bases  are  installed  and  that
polarity of the wiring is correct at each base.

Disconnect loop power before installing sensors.

1. Sensor Installation

a. Set the sensor to the desired address and record that

address on the label attached to the base.

b. Insert the sensor into the base and rotate it clockwise

until it drops into place.

c.  Continue  to  rotate  the  sensor  until  it  locks  into  the

base.

Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from enter-
ing the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity.
Be sure to remove dust covers from any sensors that were
left  in  place  during  construction  as  part  of  returning  the
system to service.