Pittway Notifier RPT-485W Скачать руководство пользователя страница 2

WARNING:

 This equipment generates, uses, and can radiate radio frequency

energy and if not installed and used in accordance with the instruction manual, may

cause interference to radio communications. It has been tested and found to comply

with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC

Rules, which is designed to provide reasonable protection against such interference

when operated in a commercial environment. Operation of this equipment in a

residential area is likely to cause interference, in which case the user will be required

to correct the interference at his own expense.

Installation Precautions 

 

-   Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING 

Several different sources of power can be connected to the fire alarm

control panel.

  Disconnect all sources of power before servicing.  Control unit and

associated equipment may be damaged by removing and/or inserting cards,

modules, or interconnecting cables while the unit is energized.  Do not attempt to

install, service, or operate this unit until this manual is read and understood.

CAUTION - 

System Reacceptance Test after Software Changes:

     To ensure

proper system operation, this product must be tested in accordance with NFPA 72-

1993 Chapter 7 after any programming operation or change in site-specific software.

Reacceptance testing is required after any change, addition or deletion of system

components, or after any modification, repair or adjustment to system hardware or

wiring.

All components, circuits, system operations, or software functions known to be

affected by a change must be 100% tested.  In addition, to ensure that other

operations are not inadvertently affected, at least 10% of initiating devices that are

not directly affected by the change, up to a maximum of 50 devices, must also be

tested and proper system operation verified.

This system  

meets NFPA requirements for operation at 0-49

O

 C/32-120

O

 F

and at a relative humidity of 85% RH (non-condensing) at 30

C/86

O

 F.

However, the useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme temperature ranges and

humidity.  Therefore, it is recommended that this system and its peripherals be

installed in an environment with a nominal room temperature of 15-27

O

 C/60-80

O

F.

Verify that wire sizes are adequate

 for all initiating and indicating device loops.

Most devices cannot tolerate more than a 10% I.R. drop from the specified device

voltage.

Like all solid state electronic devices,

 this system may operate erratically or can

be damaged when subjected to lightning induced transients.  Although no system is

completely immune from lightning transients and interferences, proper grounding will

reduce susceptibility.

 Overhead or outside aerial wiring is not recommended, due to

an increased susceptibility to nearby lightning strikes.

  Consult with the Technical

Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries

 prior to removing or inserting circuit boards.

Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing, reaming, or punching

of the enclosure. When possible, make all cable entries from the sides or rear.

Before making modifications, verify that they will not interfere with battery,

transformer, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over tightening may damage

threads, resulting in reduced terminal contact pressure and difficulty with screw

terminal removal.

This system 

contains static-sensitive components.  Always ground yourself with a

proper wrist strap before handling any circuits so that static charges are removed

from the body.  Use static suppressive packaging to protect electronic assemblies

removed from the unit.

Follow the instructions

 in the installation, operating, and programming manuals.

These instructions must be followed to avoid damage to the control panel and

associated equipment. FACP operation and reliability depend upon proper

installation.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance

rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system

 - typically made up of smoke detectors, heat

detectors, manual pull stations, audible warning devices, and a fire alarm control

with remote notification capability can provide early warning of a developing fire.

Such a system, however, does not assure protection against property damage or

loss of life resulting from a fire.

Any fire alarm system

 may fail for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot reach the detectors such

as in chimneys, in walls, or roofs, or on the other side of closed doors.  Smoke

detectors also may not sense a fire on another level or floor of a building.  A second

floor detector, for example, may not sense a first floor or basement fire.  Further-

more, all types of smoke detectors - both ionization and photoelectric types, have

sensing limitations.  No type of smoke detector can sense every kind of fire caused

by carelessness and safety hazards like smoking in bed, violent explosions,

escaping gas, improper storage of flammable materials, overloaded electrical

circuits, children playing with matches, or arson.

IMPORTANT! 

 Smoke detectors  

must be installed in the same room as the

control panel and in rooms used by the system for the connection of alarm

transmission wiring, communications, signaling, and/or power.

  If detectors are

not so located, a developing fire may damage the alarm system, crippling its

ability to report a fire.

Audible warning devices

 such as bells  may not alert people if these devices are

located on the other side of closed or partly open doors or are located on another

floor of a building.

A fire alarm system

 will not operate without any electrical power.  If AC power fails,

the system will operate from standby batteries only for a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced sensitivity over time.  For

this reason, the rate-of-rise feature of each detector should be tested at least once

per year by a qualified fire protection specialist.

Equipment used in the system

 may not be technically compatible with the control.

It is essential to use only equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a premise to a central

monitoring station may be out of service or temporarily disabled.

The most common cause

 of fire alarm malfunctions, however, is inadequate

maintenance.  All devices and system wiring should be tested and maintained by

professional fire alarm installers following written procedures supplied with each

device.  System inspection and testing should be scheduled monthly or as required

by National and/or local fire codes. Adequate written records of all inspections should

be kept.

FCC Warning

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation noise

emissions from digital apparatus set out in the Radio Interference Regulations of the

Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radioelectriques depassant les

limites applicables aux appareils numeriques de la classe A prescrites dans le

Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-

tions du Canada.

Technical Publishing

        Document PRECAULG.P65  12/31/96

www.PDF-Zoo.com

Содержание Notifier RPT-485W

Страница 1: ...Northford CT 06472 203 484 7161 FAX 203 484 7118 The RPT 485W RPT 485WF EIA 485 Annunciator Loop Repeater for Twisted Pair Wiring Fiber Optic Cable Document 15640 08 13 97 Revision B1 15640 B1 ECN 97...

Страница 2: ...f with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow...

Страница 3: ...ion Three RPT 485WF 7 Parallel Series Connection of RPT 485WFs 8 Section Four Installation 9 Mounting 9 Wiring the RPT 485W 11 Wiring the RPT 485WF 12 Connections Between the RPT 485 and EIA 485 Devic...

Страница 4: ...olated system Electrical isolation is maintained by employing separate power supplies for the source and boosted EIA 485 loops To remain isolated connections between each EIA 485 device must have a re...

Страница 5: ...EIA 485 Annunciator Loop Features 4 Extends EIA 485 distances in 4000 ft increments 4 Allows additional boosted EIA 485 loops 4 Each boosted loop increases annunciator node capacity by 32 4 EIA 485 b...

Страница 6: ...tion of both can be hung from the loop The source EIA 485 loop can extend up to 6 000 feet and have 32 EIA 485 devices including the RPT 485s hung from it An example of wiring an EIA 485 loop using RP...

Страница 7: ...annunciator loop eliminating ground loops and noise Features 4 Extends the EIA 485 loop up to 10 000 ft with a 10dB maximum guaranteed 15dB typically achievable attentuation for 820 850 nM fiber opti...

Страница 8: ...p can extend up to 6 000 feet and have 32 EIA 485 devices including the RPT 485s hung from it An example of wiring an EIA 485 loop using RPT 485WFs is pictured in Figure 3 2 Notice that both ends of e...

Страница 9: ...ew the board on using 2 4 40 screws CHS 4L Inner position only Screw 2 4 40 standoffs onto the top row of PEM studs on the CHS 4L Slide tab of board into inner slot of CHS 4L and rest on standoffs Use...

Страница 10: ...wire the RPT 485 If you are using an RPT 485WF you must use the center top knockout for the fiber optic cable Remove knockouts Mount the ABS 8R Place the RPT 485 in the box and afix into PEM standoff...

Страница 11: ...ocument 15640 Rev B1 08 13 97 P N 15640 B1 Figure 4 1 Wiring the RPT 485W NOTE For EIA 485 device terminals connections see Table 4 1 Use a power limited supply Use a power limited supply www PDF Zoo...

Страница 12: ...ument 15640 Rev B1 08 13 97 P N 15640 B1 12 NOTE For EIA 485 device terminal connection see Table 4 1 Figure 4 2 Wiring the RPT 485WF Use a power limited supply Use a power limited supply www PDF Zoo...

Страница 13: ...4 5 P4 3 P4 6 P4 4 Power Supply Batt Neg UZC 256 TB2 3 TB2 5 TB2 4 TB2 6 TB2 2 2 1 NOTE For additional information reference the respective manuals listed in Table 4 2 The ACS Series Annunciators 1584...

Страница 14: ...upply loop is limited by the minimum input voltage 18VDC measured across TB3 24V power supply common of the RPT 485W WF Calculating the maximum wiring resistance Rmax permitted for the 24V power suppl...

Страница 15: ...r connections between the RPT 485 and EIA 485 sources refer to Table 5 2 3 Most EIA 485 devices and sources manufactured by Notifier are not isolated When making reference connections to non isolated...

Страница 16: ...ct Installation Drawing Document 15331 for specific terminal connections 2 Most EIA 485 devices and sources manufactured by Notifier are not isolated When making reference connections to non isolated...

Страница 17: ...ier are not isolated When making refer ence connections to non isolated EIA 485 devices powered by separate power supplies care must be taken to ensure that only one power supply has Earth Fault detec...

Страница 18: ...Document 15640 Rev B1 08 13 97 P N 15640 B1 18 Notes www PDF Zoo com...

Страница 19: ...19 Document 15640 Rev B1 08 13 97 P N 15640 B1 Notes www PDF Zoo com...

Страница 20: ...itutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases p...

Отзывы: