![Pittway Notifier NIB-96 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/pittway/notifier-nib-96/notifier-nib-96_manual_1560287026.webp)
Document 15666 Rev. D 9/19/96
26
or
Section Ten: AFP-200 Slaves
Mechanical Installation
In an AFP-200 Slave application, the NIB-96 must be powered by its AM2020/
AFP1010 master. Therefore, the NIB-96 should be mounted in the AM2020/
AFP1010 master.
Plug the NIB-96 into a slot on the ICA-4/4L chassis. If the AM2020/AFP1010 is in
an A-size cabinet (only one ICA-4/4L) the NIB mounts beneath the CPU or the SIB.
If a second or third ICA-4/4L chassis is available, it is recommended that the NIB
should be mounted in one of the two upper slots to permit easy access to NIB wir-
ing and switch settings. Note that the NIB mechanically eliminates one LIB posi-
tion, and in some instances, could require the installation of an additional chassis.
As an alternative, the AM2020/AFP1010 may use a CHS-4 chassis to mount the
NIB. See Figure 4-1 for mounting the NIB in a CHS-4 chassis. The AM2020/
AFP1010 does not require that LIB boards be installed in consecutive positions.
In some applications, it may be necessary to install more than one NIB. The NIB
can be configured so that up to 4 may be installed, completely filling an ICA-4/4L
chassis.
Figure 10-1 Mounting the NIB in an ICA-4/4L Chassis
Technical Manuals Online! - http://www.tech-man.com