Pitco MG14S-C/MFD Скачать руководство пользователя страница 9

5

Chapter 2: COMPONENT

TROUBLESHOOTING:

Probe:

The resistance of the probe will change as the tem-
perature changes. The resistance will decrease as the
temperature rises. The lower the temperature the
greater the resistance change will be per degree of
temperature change, as the temperature approaches
the working range of the probe, the resistance change
will become more linear.
If the probe is suspect, check its resistance and the
oil/air temperature at which it was taken. Compare
these values on the chart below.

TEMP

RESISTANCE

TEMP

RESISTANCE

ºF

Ohms

ºF

Ohms

60

139055

330

1192

80

84644

335

1123

100

53146

340

1058

120

34328

345

998

140

22755

350

942

160

15446

355

890

180

10716

360

841

200

7586

365

795

210

6427

370

752

220

5470

375

712

240

4013

380

675

260

2991

385

640

280

2262

390

607

300

1734

395

576

320

1347

400

547

325

1267

If the probe returns an open circuit or 0 Ohms read-
ing it should be replaced. If the resistance varies more
than 20 Ohms from the above chart when being
checked between 325-375°F (162ºC - 190ºC) the
probe will give a false temperature reading on the
computer and should be replaced. However, it will
continue to operate at a slightly higher or lower tem-
perature. Allow the oil to cool and check the probe
resistance at a lower temperature. As can be seen
from the chart a greater degree of offset can be al-

lowed at a lower temperature.

Relays:

The Heat Demand and Hood relays are 24VDC re-
lays and will energize when the correct voltage is
supplied to the coil. When energizing, the relay
Switching Contacts will close, thus connecting the
Common and Normally Open terminals. The Hi -
Limit relay is a 24VAC relay and may be checked in
the same manner as the above relay.

Hi Limits:

A Hi - Limit switch is a normally closed switch until
the temperature at the probe reaches 435ºF ± 15°
(225ºC ± 15º). In order to test this switch it will be
necessary to bypass the Heat Demand Relay. Follow
the Hi Limit testing proceedure outlined on page 8
of the Operating Manual.

WARNING

Do NOT leave the machine during this test. This
test will cause the oil to heat past the normal oper-
ating temperature and can cause damage to the
machine and its operator.

If the switch does not trip between the prescribed
limits it is defective and should be replaced. Once
tripped, the switch will not reset until the oil has
cooled to approximately 400°F (204ºC). If the switch
does not reset it is defective.

Drain Valve & Return Valve Switches:

This switch is a magnetically operated Reed switch.
When the Drain Valve handle is  moved to the open
position, the Actuator will move away from the
switch causing the Reed switch to open. When the
Drain Valve is closed the Reed switch will close.
This switch can also be checked with an Ohm meter.
The normal gap between the Actuator and the Sen-
sor switch on the Drain Valve handle is 

1

/

8

" - 

1

/

4

" (3 -

6 mm).

Содержание MG14S-C/MFD

Страница 1: ...Rev Date January 2002 Made in the United States of America GAS FRYER with FILTER MODEL MG14S C MFD MANUFACTURED EXCLUSIVELY FOR McDONALD S PITCO FRIALATOR INC P O BOX 501 CONCORD NH 03302 0501 Phone 1...

Страница 2: ...carbon monoxide gas Carbon Monoxide is a clear odorless gas that can cause suffocation WARNING Carbon Monoxide gas can build up if you obstruct the flue Blocking the flue will also cause the unit to o...

Страница 3: ...nvolved in replacing said part 2 WARRANTY PROVISIONS FRYPOTS A If a frypot develops a leak due to a defect in material or workmanship within the first 10 years after installation Pitco Frialator Inc w...

Страница 4: ...3 Hood Relay System 3 Chapter 2 COMPONENT TROUBLESHOOTING 5 Probe 5 Relays 5 Hi Limits 5 Drain Valve Return Valve Switches 5 Transformer 6 Blower 6 Pressure Switch 6 Gas Valve 6 Chapter 3 TROUBLESHOOT...

Страница 5: ...rical Code Part 1 NOTE Should you experience a power failure your fryers will shut off automatically If this happens do not attempt to restart the fryers until the power is restored Ventilation A prop...

Страница 6: ...gram is located in the back of this manual and inside the fryers The control interlock voltage for this equipment must be 120 VAC US Canada For other coun tries please check the rating plate Regular c...

Страница 7: ...il reenergized On Split Vat machines the same power that supplies the computer also supplies 24 VAC to the normally open Pressure Switch S9 When the computer en ergizes the Heat Demand Relay K1 the Bl...

Страница 8: ...4 Full Vat Fryers Split Vat Fryers...

Страница 9: ...ee of offset can be al lowed at a lower temperature Relays The Heat Demand and Hood relays are 24VDC re lays and will energize when the correct voltage is supplied to the coil When energizing the rela...

Страница 10: ...acuum falls below ap proximately 0 8 WC 0 2 kPa the Pressure Switch will open With the Blower running check the IN and OUT voltage of the Switch If 24VAC can be found on one side but NOT the other the...

Страница 11: ...s Valve Relay Full Vat Only G Check and replace as needed H Tripped or defective Hi Limit H Allow the oil to cool the Hi Limit will reset itself Turn the computer OFF and back ON again to reset the co...

Страница 12: ...to check that it is still shows DRAINING or B Sensor switch may be loose or bad fully closed TURN OFF B Check that the switch is tight in its mounting If switch is bad replace it Drain Valve is OPEN...

Страница 13: ...he reverse order Computers CAUTION Take care not to drop any of the components from the front panel as this will damage them 1 Remove the two screws from the upper mount of the front panel 2 Unplug th...

Страница 14: ...n the following man ner Control Relays Control relays are always wired in the following man ner Filter Pumps 1 From the front of the machine pull the ring back on each of the 2 quick disconnects and r...

Страница 15: ...t the top of the gas valve 2 Unscrew the pipe union located behind the gas valve 3 Unplug the 3 wires that plug into the gas valve Install in the reverse order Burners and Spark Ignitors NOTE If the i...

Страница 16: ...wered out of the ma chine NOTE The new blower will be shipped with the blower housing attached Remove the motor from the blower housing in the above manner Clean the sealant from the new motor and the...

Страница 17: ...hine 2 Remove the burners and ignitors from the vat to be removed 3 Disconnect the drain valve switch wires 4 Disconnect the return valve switch wires 5 Disconnect the blower wires 6 Remove the drain...

Страница 18: ...ttom of the vat at the front NOTE To disconnect the filter return piping as in step 15 unscrew the union connecting the return piping to the vats Install in the reverse order 13 Remove the complete sp...

Страница 19: ...15...

Страница 20: ...16 PARTS SECTION...

Страница 21: ...BEZLE ASSEMBLY 9 P0092300 10 24 HEX NUT 10 P0080601 10 FLAT WASHER 11 PP11372 3600 McDONALDS COMPUTER FULL SPLIT VAT 12 B362601 C CONTROLLER MOUNTING BEZLE 13 PP11068 HEAT DEMAND RELAY P5046688 MAIN G...

Страница 22: ...18...

Страница 23: ...UAD FRYER CABINET BACK USE DUAL TRIPLE QUINT FRYER CABINET BACK 5 P0020600 1 4 X 5 8 BOLT 6 PP10815 9 LOCKING CASTER 6 PP10814 9 NON LOCKING CASTER 7 P0093300 1 4 X 20 NUT 8 B3622401 C SINGLE FRONT PA...

Страница 24: ...20...

Страница 25: ...heat tape B6638602 C PUMP MOTOR ASSEMBLY 240VAC Including tubing heat tape B6638603 C PUMP MOTOR ASSEMBLY 220VAC Pump motor only PP10101 PUMP MOTOR ASSEMBLY 115 230VAC PP10416 MOTOR ONLY 115 230VAC Pu...

Страница 26: ...22...

Страница 27: ...8 B6640601 C FILTER DRAWER WELDMENT 9 PP11152 ROLLER WHEEL KIT 10 B6656801 C FILTER DRAWER EXTENSION RAIL RH B6656802 C FILTER DRAWER EXTENSION RAIL LH 11 A7008302 PAPER SUPPORT RACK 12 B6661501 C FIL...

Страница 28: ...24...

Страница 29: ...T 4 PP10266 4 40 X 1 4 SCREW 5 PP10647 1 2 13 NUT 6 PP11059 PLUNGER ASSEMBLY 7 A4015801 DRAIN HANDLE RELEASE LEVER 8 PP11303 RELEASE LEVER VINYL COVER 9 B4003001 C FULL VAT HANDLE ASSEMBLY Complete dr...

Страница 30: ...26...

Страница 31: ...P11064 HI LIMIT SWITCH 6 PP11193 FLAME SENSOR CE 7 B3316801 C TEMPERATURE PROBE ASSY 8 CALL SERVICE AGENT FOR BURNER ORIFICE 9 PP11140 GAS VALVE NAT DOMESTIC PP11142 GAS VALVE NAT CE PP11141 GAS VALVE...

Страница 32: ...28...

Страница 33: ...PIECE B5002703 C QUAD CAPPING PIECE B5002704 C QUINT CAPPING PIECE 6 A1907004 CHANNEL STRIP INTERIOR OF A SPLIT 7 A1907504 CHANNEL STRIP SPLIT TO SPLIT TANK A1906804 CHANNEL STRIP SPLIT TO FULL FULL T...

Страница 34: ...30...

Страница 35: ...IT SWITCH PRESSURE PROBE THERMISTOR V1 TB1 P5045281 PP11140 TERMINAL BLOCK 6 POSITION VALVE GAS 24VAC NAT T1 PP10210 TRANSFORMER 40VA 120 208 240V TO24V CB1 PP10460 SWITCH CIRCUIT BREAKER SPST 8A 250V...

Страница 36: ...32 HEAT TAPE OPTION NOTES 1 FILTER OPTION 2ND LEFT HAND FRYER ONLY 2 ALL WIRE 18GA UNLESS OTHERWISE SPECIFIED 700250...

Страница 37: ...ER 115V 60HZ 3200 RPM PP10208 P5045829 PP10101 PP11067 PP11058 P5045839 PP10089 PP11033 PARTS LIST 700251 COMPUTER 3620 14 MLB FUSE 2A SLOW BLOW SWITCH CIRCUIT BREAKER PART NO PP10209 P5045717 PP10460...

Страница 38: ...USED ON FILTER OPTION W O HEAT TAPE ONLY HEAT TAPE THERMOSTAT 1 2 3 2 1 1 2 1 12 1 8 2 9 4 7 3 11 10 6 5 12 11 1 8 2 9 7 4 3 6 5 10 2 1 BK W 2 1 3 2 1 2 1 GAS VALVE 2 1 J5 P5 RT2 2 1 GAS VALVE ONLY L...

Страница 39: ...ntative ASAP cov eringyouarea throughtheNationalServiceNetwork at 800 298 1862 US only 24 hours Intheeventofproblemswithorquestionsaboutyour order please contact the Pitco Frialator factory from 8 00...

Отзывы: