Output
Current consumption
Pressure detection
Operating pressure range
Pressure setting range
Proof pressure
Operating temp. range
Operating humidity range
Power requirements
Protective structure
#
of pressure setting
Operating accuracy
Differential response
Switch output
Analog output
Differential response
Indication
Display frequency
Indication accuracy
Sensor resolution
Operational indication
Function
2 switch output (-PW)
1 switch and 1 analog output (-PA)
40mA or less
Diffused metaloxide semiconductive pressure transducer
0 ~ -99kPa
29psi (
0.2MPa
)
35 ~ 85%RH (No dew condensation)
12 ~ 24VDC
±
10% Ripple (P-P) 10% max.
IEC standard IP40 equiv.
2
1
±3%F.S. max. (at Ta=25°C)
Fixed (2%F.S. max.)
PNP open collector output: Supply voltage 80mA max. Residual
Variable (about 0 ~ 15% of set value)
Output voltage
1 ~ 5V
Zero-point voltage
1±0.1V
Span voltage
4±0.1V
Output current Output current: 1mA max. (load resistance 50k
Ω
max.)
LIN
/
HYS
±0.5%F.S. max.
approx. 2m·sec max.
0 ~ -99kPa (2-digit red LED display)
About 4 times / sec.
±3%F.S. ±2 digit
1 digit
Red LED turns ON, when pressure is above the setting
1. MODE selector switch (ME / SW)
2. SW setting trimmer (2/3- turn trimmer)
3. HYS setting trimmer (About 0-15% of setting value)
SW1: Red LED turns ON, when pressure is above the setting
SW2: Green LED turns ON, when pressure is above the setting
1. MODE selector switch (ME / S1 / S2)
2. S1 setting trimmer (2/3-turn trimmer)
3. S2 setting trimmer (2/3- turn trimmer)
■
PNP open collector
(
0 ~ 50°C
)
(No freezing)
32 ~ 1
20
°
F
0
~
-
29.5inHg (
0 ~ -100kPa
)
http://www.pisco.com
Содержание VK Series