Environmental data

777587

787587

Airgap creepage

In accordance with the standard

EN 60947-1

EN 60947-1

Overvoltage category

III

III

Pollution degree

2

2

Rated insulation voltage

250 V

250 V

Rated impulse withstand voltage

6 kV

6 kV

Protection type

Housing

IP40

IP40

Terminals

IP20

IP20

Mounting area (e.g. control cab-
inet)

IP54

IP54

Mechanical data

777587

787587

Mounting position

Any

Any

Mechanical life

10,000,000 cycles

10,000,000 cycles

Material

Bottom

PPO UL 94 V0

PPO UL 94 V0

Front

ABS UL 94 V0

ABS UL 94 V0

Top

PPO UL 94 V0

PPO UL 94 V0

Connection type

Screw terminal

Spring-loaded terminal

Mounting type

plug-in

plug-in

Conductor cross section with screw
terminals

1 core flexible

0,25 - 2,5 mm², 24 - 12 AWG

2 core with the same cross sec-
tion, flexible with crimp connect-
ors, no plastic sleeve

0,25 - 1 mm², 24 - 16 AWG

2 core with the same cross sec-
tion, flexible without crimp con-
nectors or with TWIN crimp con-
nectors

0,2 - 1,5 mm², 24 - 16 AWG

Torque setting with screw terminals

0,5 Nm

Stripping length with screw termin-
als

8 mm

Conductor cross section with
spring-loaded terminals: Flexible
with/without crimp connector

0,2 - 1,5 mm², 24 - 16 AWG

Spring-loaded terminals: Terminal
points per connection

2

Stripping length with spring-loaded
terminals

8 mm

Dimensions

Height

94 mm

101 mm

Width

22,5 mm

22,5 mm

Depth

121 mm

121 mm

Weight

185 g

185 g

Where standards are undated, the 2020-07 latest editions shall apply.

Содержание PZE X4.1P

Страница 1: ...PZE X4 1P Operating Manual 1003203 EN 09 Safety relays...

Страница 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Страница 3: ...lity 6 Disposal 6 For your safety 6 Unit features 7 Safety features 7 Block diagram terminal configuration 8 Type DC 8 Type AC DC 8 Function description 9 Installation 9 Wiring 9 Preparing for operati...

Страница 4: ...larly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measur...

Страница 5: ...nt technical or electrical modification to the product Use of the product outside the areas described in this manual Use of the product outside the technical details see Technical details 12 NOTICE EM...

Страница 6: ...wledge of the generic and specialist standards applicable to the specific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contr...

Страница 7: ...l See order reference for unit types Safety features The unit meets the following safety requirements The contact expansion module expands an existing circuit As the output relays are mon itored via t...

Страница 8: ...X4 1P Safe separation from non marked area in accordance with EN 60947 1 6 kV basic insulation between all safety contacts Type AC DC UB 24 240 VAC DC Order no 777588 787588 PZE X4 1P Insulation betwe...

Страница 9: ...When installed vertically Secure the unit by using a fixing element e g retaining bracket or end angle Wiring Please note Information given in the Technical details 12 must be followed The outputs 13...

Страница 10: ...A2 L L Input circuit Single channel Dual channel Base unit Safety relay PNOZ X Driven via safety contacts K1 K2 U PZE K1 K2 U PZE Base unit PNOZelog safety relay program mable safety system or PNOZmul...

Страница 11: ...SIL CL 3 PL e at least 1x per month for SIL CL 2 PL d at least 1x per year NOTICE The safety function should be checked after initial commissioning and each time the plant machine is changed The safet...

Страница 12: ...s Listed CCC CE EAC Eurasian T V cULus Listed Electrical data 777587 787587 Supply voltage Voltage 24 V 24 V Kind DC DC Voltage tolerance 15 10 15 10 Output of external power supply DC 2 5 W 2 5 W Res...

Страница 13: ...at 24 V 24 V Min current 0 01 A 0 01 A Max current 6 A 6 A Max power 150 W 150 W Utilisation category In accordance with the standard EN 60947 5 1 EN 60947 5 1 Utilisation category of safety con tacts...

Страница 14: ...power on max 30 ms 30 ms Delay on de energisation With E STOP typ 10 ms 10 ms With E STOP max 20 ms 20 ms With power failure typ 60 ms 60 ms With power failure max 80 ms 80 ms Supply interruption bef...

Страница 15: ...ring loaded terminal Mounting type plug in plug in Conductor cross section with screw terminals 1 core flexible 0 25 2 5 mm 24 12 AWG 2 core with the same cross sec tion flexible with crimp connect or...

Страница 16: ...ual ripple DC 20 20 Duty cycle 100 100 Inputs 777588 787588 Number 2 2 Voltage at Input circuit DC 24 V 24 V Current at Input circuit DC 30 mA 30 mA Max overall cable resistance Rl max Single channel...

Страница 17: ...U same polarity 250 V AC G U same polarity With current 6 A 6 A Voltage 24 V DC G U 24 V DC G U With current 6 A 6 A Pilot Duty B300 R300 B300 R300 External contact fuse protection safety contacts In...

Страница 18: ...With power failure typ UB 240 V 1300 ms 1300 ms With power failure max UB 240 V 1900 ms 1900 ms With power failure typ UB 24 V 270 ms 270 ms With power failure max UB 24 V 350 ms 350 ms Supply interru...

Страница 19: ...Spring loaded terminal Mounting type plug in plug in Conductor cross section with screw terminals 1 core flexible 0 25 2 5 mm 24 12 AWG 2 core with the same cross sec tion flexible with crimp connect...

Страница 20: ...as the proof test interval and mission time in accordance with EN 62061 All the units used within a safety function must be considered when calculating the safety characteristic data INFORMATION A saf...

Страница 21: ...mainly caused by the electrical load the mechanical load is negli gible 10000 1000 5000 100 500 10 50 0 1 0 5 1 2 3 4 5 6 8 10 DC 1 24V DC 1 24V AC 1 230V AC 1 230V AC 15 230V AC 15 230V DC 13 24V DC...

Страница 22: ...ith capacitive loads any power surges that occur must be noted With DC contact ors use flywheel diodes for spark suppression Remove plug in terminals Procedure Insert the screwdriver into the housing...

Страница 23: ...meet the requirements of the directive 2006 42 EC for ma chinery of the European Parliament and of the Council The complete EC Declaration of Conformity is available on the Internet at www pilz com do...

Страница 24: ...energy efficient products and environmentally friendly solutions We are represented internationally Please refer to our homepage www pilz com for further details or contact our headquarters Headquart...

Отзывы: