All errors and faults detected by the electronic modules on a PSSu are
signalled to the head module and entered in the head module's error
stack. You can read the head module's error stack using the
PSS WIN-PRO system software (SafetyBUS p, Domain 0).
][BA_Betrieb Tabelle Meldungen FS
Module error
Explanation
Remedy
Start-up error
Error as the PSSu system starts up
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry does
not match the actual hardware regis-
try.
FS communication error
Error during FS communication
Change faulty module.
Bus termination error
There is no terminating plate or there is
a bad contact with the module bus.
Install a terminating plate with inte-
grated end bracket or insert the base
modules together correctly.
Temperature error: Too warm (
1
)
Ambient temperature too high:
Error stack entry
Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.
Temperature error: Too hot (
1
)
Ambient temperature too high:
Reset the module and stop the affect-
ed I/O-Groups (SafetyBUS p)
Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.
Output error
Error during cyclical output test for
short circuit. Possible causes: Short
circuit, or output defective.
Rectify the short circuit or change the
faulty module.
Test pulse error
Possible causes: Short circuit be-
tween a test pulse and a supply volt-
age, or a defective module.
Rectify the short circuit or change the
faulty module.
Relay control error
Error during cyclical monitoring test of
the relay coils
Change faulty relay module.
Relay error
A relay position is faulty. Possible
cause: Defective relay contact
Change faulty relay module.
Block switching output error
Error during cyclical monitoring test of
the relay contacts. Possible external
cause: Voltages being fed back to the
relay contacts
Check the supply voltage and the wir-
ing.
Error in the feedback loop
FS input detects an error in the feed-
back loop or FS input is defective.
Check FS input, check the configura-
tion of the feedback loop, check the
signals, or check the wiring and con-
tacts.
Error in the local enable principle
FS output has reacted incorrectly or
unexpectedly
Check the configuration of the FS out-
put or check the fieldbus signals in the
FS and ST section.
Input error
Error during the cyclical input test.
Possible cause: Input defective.
Change faulty module.
Overvoltage error
A system voltage or infeed is too high. Stabilise the supply or change the
faulty supply voltage module.