Technical details
Operating Manual PSSu E S 2AO U(-T)
21423-EN-04
33
Analogue outputs
312460
314460
Potential isolation between output
and voltage for the internal module
bus
yes
yes
Potential isolation between output
and periphery supply
yes
yes
Typ. processing time of the ana-
logue output
1,0 ms
1,0 ms
Environmental data
312460
314460
Climatic suitability
EN 60068-2-1, EN 60068-2-14, EN
60068-2-2, EN 60068-2-30, EN
60068-2-78
EN 60068-2-1, EN 60068-2-14, EN
60068-2-2, EN 60068-2-30, EN
60068-2-78
Ambient temperature
In accordance with the standard
EN 60068-2-14
EN 60068-2-14
Temperature range
0 - 60 °C
-40 - 70 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
EN 60068-2-1/-2
Temperature range
-25 - 70 °C
-40 - 70 °C
Climatic suitability
In accordance with the standard
EN 60068-2-30, EN 60068-2-78
EN 60068-2-30, EN 60068-2-78
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Short-term
EMC
EN 61000-4-2, EN 61000-4-3, EN
61000-4-4, EN 61000-4-5, EN
61000-4-6, EN 61000-6-2, EN
61000-6-4
EN 61000-4-2, EN 61000-4-3, EN
61000-4-4, EN 61000-4-5, EN
61000-4-6, EN 61000-6-2, EN
61000-6-4
Vibration
In accordance with the standard
EN 60068-2-6
EN 60068-2-6
Frequency
10,0 - 150,0 Hz
10,0 - 150,0 Hz
Amplitude
0,35 mm
0,35 mm
Acceleration
1g
1g
Broadband noise
In accordance with the standard –
EN 60068-2-64
Frequency
–
5 - 500 Hz
Acceleration
–
1,9grms
Shock stress
In accordance with the standard
EN 60068-2-27
EN 60068-2-27
Number of shocks
6
6
Acceleration
15g
15g
Duration
11 ms
11 ms
In accordance with the standard
EN 60068-2-27
EN 60068-2-27
Number of shocks
1000
1000
Acceleration
10g
10g
Duration
16 ms
16 ms
Max. operating height above sea
level
2000 m
5000 m