20
PSSnet SLL
Pilz GmbH & Co. KG, Felix- Wankel- Straße 2, 73760 Ostfildern, Germany
Network range
MM = Multimode, SM = Singlemode
Power consumption/power output at 24 V DC
IEC/EN 61000-4-5 Voltage surges
DC power line, line / line
DC power line, line / earth
Data line, line / earth
+/- 1 kV
+/- 2 KV
+/- 1 kV
IEC/EN 61000-4-6 Line-conducted interference voltages
150 kHz - 80 MHz
10 V
EMC emitted interference
EN 55022
Class A
FCC 47 CFR Part
15
Class A
Stability
Vibration
IEC 60068-2-6, test Fc
5 Hz to 9 Hz with 3.5 mm amplitude;
1g at 9 Hz to 150 Hz;
1.5 g at 200 Hz to 250 Hz
IEC 60068-2-6, resonance search /
resonance dwell, test Fc
2 Hz to 13.2 Hz with 1 mm ampli-
tude;
0.7 g at 13.2 Hz to 100 Hz
Shock
IEC 60068-2-27 test Ea
15 g at 11 ms
TP port
Length of a twisted pair segment
max. 100 m / 300 ft
Table 4: TP port 10BASE-T / 100BASE-TX
Product code
F/O
type
Wave
length
Fiber
System at-
tenuation
Expansion Fiber data
PSSnet SLL 4T
1FMMSC
MM
1300 nm 50/125
μ
m
0-8 dB
0-5 km
1.0 dB/km;
800 MHz*km
PSSnet SLL 4T
1FMMSC
MM
1300 nm 62.5/125
μ
m 0-11 dB
0-4 km
1.0 dB/km;
500 MHz*km
Table 5: F/O port 100BASE-FX
Device name
Max. power consumption
Power output
PSSnet SLL 5T
2.2 W
7.5 Btu (IT)/h
PSSnet SLL 4T 1FMMSC
3.9 W
13.3 Btu (IT)/h
EMC interference immunity