Pilz PSEN ma1.4p-51 Скачать руководство пользователя страница 17

PSEN ma1.4p-51

Operating Manual PSEN ma1.4p-51
22127-EN-05

17

}

7. Installation of sensor and actuator is now complete.

1

2

3

4

5

6

7

INFORMATION

Seals (1), (2), (3) meet the requirements of UL 94 V0, seal (4) does 

not

meet UL requirements.

Adjustment

}

The safety switch may only be used with the corresponding actuator PSEN ma1.4-03 or
PSEN ma1.4-10.

}

Always test the function with a connected evaluation device.

}

The stated operating distances (see 

Technical details [

 18]

) only apply when the

safety switch and actuator are installed according to the specifications

Installation [

 14]

. Operating distances may deviate if other arrangements are used.

Note the maximum permitted lateral and vertical offset (see 

Operating distances and

Lateral and vertical offset [

 8]

).

Periodic test

}

Carry out a monthly function test on the safety switch and actuator.

}

Always test the function with a connected evaluation device.

}

The safety function may only be checked by qualified personnel.

Содержание PSEN ma1.4p-51

Страница 1: ...PSEN ma1 4p 51 Operating Manual 22127 EN 05 PSEN sensor technology...

Страница 2: ...umentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Interne...

Страница 3: ...ty 6 Disposal 6 For your safety 6 Unit features 7 Function description 7 Block diagram 8 Operating distances 8 Lateral and vertical offset 9 Wiring 10 Pin assignment 10 Requirements and connection to...

Страница 4: ...particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive...

Страница 5: ...side the technical details see Technical details 18 NOTICE EMC compliant electrical installation The product is designed for use in an industrial environment The product may cause interference if inst...

Страница 6: ...d liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the guidelines in the manual Operating per...

Страница 7: ...tor see Technical details 18 Design Safety switch with square design Actuator with square design PSEN ma1 4 03 Actuator with square design PSEN ma1 4 10 Operation Magnetic Switching voltage 24 VDC LED...

Страница 8: ...or Safety switch Magnet 7 1 4 2 6 3 Operating distances Sao So Sr Sar mm Somin On Off Legend Sao Assured operating distance Somin Min operating distance Sar Assured release distance The offset indepen...

Страница 9: ...Lateral offset 0 1 2 3 4 0 3 0 3 0 2 5 1 5 1 0 1 3 0 2 5 2 0 0 5 2 2 5 1 5 1 0 3 1 5 0 5 4 0 5 The stated values are valid at a temperature of 20 C Actuator PSEN ma1 4 10 Assured operating distance S...

Страница 10: ...ck the function that detects shorts across contacts prior to commissioning On evaluation devices with DC supply voltage Overall cable resistance 15 Ohms per channel On evaluation devices with AC suppl...

Страница 11: ...ice with defined properties Certified Pilz evaluation devices are for example PNOZelog for safety gate monitoring PNOZ e1p PNOZ e1 1p PNOZ e1vp PNOZ e5 11p PNOZ e6vp PNOZ e6 1p PNOZpower for safety ga...

Страница 12: ...data of the evaluation device must fulfil the requirements in the Technical details 18 of PSEN ma1 4p 51 Always comply with the max switching current safety contacts of PSEN ma1 4p 51 Outputs at the e...

Страница 13: ...1 2 3 4 7 6 Pink green white yellow Auxiliary contact with LED The auxiliary contact and the LED indicate the status of the safety contacts Actuator in the response range Safety contacts and auxili a...

Страница 14: ...the release distance Sar with non flush installation Installing the safety switch non flush within electrically or magnetically con ductive material the value for the assured release distance Sar can...

Страница 15: ...assured operating distance Sao and the assured release distance Sar must be tested under real conditions Installation type 1 1 Cut the thread M4 in the required position 2 Use a screw to fix the sens...

Страница 16: ...n for installation type 1 1 Attach the screws for the actuator maintaining the distance between the screw head and the plate ca 3 6 mm 2 Close unused mounting holes on the plate using seal 2 see Diagr...

Страница 17: ...ected evaluation device The stated operating distances see Technical details 18 only apply when the safety switch and actuator are installed according to the specifications Installation 14 Operating d...

Страница 18: ...V cULus Listed Sensor s mode of operation Magnetic Magnetic Coding level in accordance with EN ISO 14119 Low Low Design in accordance with EN ISO 14119 4 4 Classification in accordance with EN 60947...

Страница 19: ...EN 60947 5 2 Frequency 10 55 Hz 10 55 Hz Amplitude 1 mm 1 mm Shock stress Acceleration 30g 30g Duration 11 ms 11 ms Airgap creepage Pollution degree 3 3 Rated insulation voltage 25 V 25 V Rated impul...

Страница 20: ...d the 2015 09 latest editions shall apply Safety characteristic data NOTICE You must comply with the safety related characteristic data in order to achieve the required safety level for your plant mac...

Страница 21: ...inkel cable angleplug 10m Female connector M8 angled 4 pin 10 m 533 130 PSEN Kabel Gerade cable straightplug10m Female connector M8 straight 4 pin 10 m 533 131 PSEN Kabel Winkel cable angleplug 3m Fem...

Страница 22: ...fetyNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document d...

Отзывы: