PSEN 2.1b-26
Operating Manual PSEN 2.1b-26
21380-EN-12
| 9
Lateral and vertical offset
[1]
[2]
Legend
[1] Lateral offset
[2] Vertical offset
Actuator PSEN 2.1-20
The stated values are valid at a temperature of 20 °C.
Assured operating distance S
ao
in mm
Vertical offset
Lateral offset
1.0
1.5
2.0
2.5
3.0
1
7.5
7.5
7.5
7.0
7.0
2
7.5
7.5
7.0
7.0
7.0
3
7.0
7.0
7.0
6.5
6.5
4
6.5
6.5
6.5
6.5
6.5
5
6.0
6.0
6.0
5.5
5.5
Wiring
}
Information given in the
Technical details [
17]
must be followed.
}
Calculation of the max. cable length l
max
:
R
lmax
- R
i
R
l
/ km
I
max
=
R
lmax
= Max. overall cable resistance (see evaluation device's technical details)
Ri = Internal resistance sensor (see
Technical details [
17]
)
R
l
/ km = Cable resistance/km of the cable (see technical details cable)
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
Depending on which evaluation device is used, the overall cable resistance must be
checked; before commissioning it may also be necessary to check the cross circuit detec-
tion function.
}
Make sure that the safety switch cable extends from the EX area into the non-Ex area
and that the cable connection is within the non-Ex area.
}
Protect the safety switch's electrical connections from corrosion.
}
The safety contacts are not short circuit-proof.