PNOZ XV3P
Operating Manual PNOZ XV3P
20122-EN-05
18
Relay outputs
777510
777512
777514
Number of output con-
tacts
Safety contacts (N/O),
instantaneous
3
3
3
Safety contacts (N/O),
delayed
2
2
2
Max. short circuit current
IK
1 kA
1 kA
1 kA
Utilisation category
In accordance with the
standard
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
Utilisation category of
safety contacts
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category of
safety contacts delayed
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Utilisation category of
safety contacts
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A
Utilisation category of
safety contacts delayed
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A