PNOZ XV2.1
Operating Manual PNOZ XV2.1
20690-EN-08
| 16
Relay outputs
774550
774552
774558
Utilisation category
In accordance with the
standard
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
Utilisation category of
safety contacts
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category of
safety contacts delayed
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Utilisation category of
safety contacts
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A
Utilisation category of
safety contacts delayed
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A
Utilisation category in ac-
cordance with UL
Voltage
240 V AC G. P.
240 V AC G. P.
240 V AC G. P.
With current
8 A
8 A
8 A
Pilot Duty
C300, R300
C300, R300