![Pilz PNOZ X2.8P Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/pilz/pnoz-x2-8p/pnoz-x2-8p_operating-manual_1556847024.webp)
PNOZ X2.8P
Operating Manual PNOZ X2.8P
1004082-EN-20
| 24
Relay outputs
787301
787302
Utilisation category in accordance
with UL
Voltage
240 V AC G.U. (same polarity)
250 V AC G.U. (same polarity)
With current
6 A
6 A
Voltage
24 V DC G. P.
24 V DC G. P.
With current
6 A
6 A
Pilot Duty
R300
B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
260 A²s
66 A²s
Blow-out fuse, quick
10 A
6 A
Blow-out fuse, slow
6 A
4 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24V AC/DC,
characteristic B/C
6 A
4 A
External contact fuse protection,
auxiliary contacts
Max. melting integral
160 A²s
66 A²s
Blow-out fuse, quick
10 A
6 A
Blow-out fuse, slow
6 A
4 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24 V AC/DC,
characteristic B/C
6 A
4 A
Contact material
0,2 µm Au
0,2 µm Au
Conventional thermal current
while loading several contacts
787301
787302
Ith per contact at UB AC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-
tact
6 A
6 A
Conv. therm. current with 2 con-
tacts
4 A
6 A
Conv. therm. current with 3 con-
tacts
3,5 A
4,5 A
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-
tact
6 A
6 A
Conv. therm. current with 2 con-
tacts
6 A
6 A
Conv. therm. current with 3 con-
tacts
5 A
4,5 A