PNOZ X2.1VP
Operating Manual PNOZ X2.1VP
20211-EN-07
8
Function Description
The safety relay PNOZ X2.1VP provides a safety-oriented interruption of a safety circuit.
When supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation
when the start circuit S33-S34 is closed.
}
Input circuit is closed (e.g. E-STOP pushbutton not operated):
– The LEDs "CH.1" and "CH.2" are lit.
– Safety contacts 27-28 and 37-38 are closed. The unit is active.
– The semiconductor output Y11-Y12 is enabled.
– The "ON" LED is lit.
}
Input circuit is opened (e.g. E-STOP pushbutton operated):
– The semiconductor output Y11-Y12 is disabled instantaneously.
– The "ON" LED goes out.
– Safety contacts 27-28 and 37-38 are opened redundantly after the delay time has
elapsed.
– The LEDs "CH.1" and "CH.2" go out.
Operating modes
}
Single-channel operation: No redundancy in the input circuit, earth faults in the start
and input circuit are detected.
}
Dual-channel operation with detection of shorts across contacts: Redundant input cir-
cuit, PNOZ X2.1VP detects
– earth faults in the start and input circuit,
– short circuits in the input circuit,
– shorts across contacts in the input circuit.
}
Automatic start: Unit is active once the input circuit has been closed.
}
Manual start: Unit is active once the input circuit and the start circuit are closed.
}
Increase in the number of available contacts by connecting contact expander modules
or external contactors/relays.