PNOZ po3.1p
Operating Manual PNOZ po3.1p
20676-EN-07
9
Power supply Base unit
Expansion module 1
Expansion module 4
95579
Terminator
95579
Terminator
95425
Jumper
Order no: 779120
Order no: 779120
Order no: 774639
PNOZ po3.1p
WARNING!
Risk of electrocution!
When voltage is applied, contact with live components could result in seri-
ous or even fatal injury from an electric shock.
The plug-in connection terminals should only be connected and disconnec-
ted when the voltage is switched off.
Wiring
Please note:
}
Information given in the "
Technical details [
12]
" must be followed.
}
The outputs 13-14, 23-24, 33-34, 43-44, 53-54, 63-64, 73-74, 83-84 are safety con-
tacts.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [
12]
).
}
Use copper wire that can withstand 60/75 °C.
}
Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.
}
Do not switch low currents using contacts that have been used previously with high cur-
rents.
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.