Wiring

Please note:

}

Information given in the "

Technical details [

 10]

" must be followed.

}

Max. cable runs I

max

 at the input circuit and feedback loop: Short circuits and earth faults

are detected by the master controller. The maximum cable runs is therefore dependent
on the master controller.

}

Use copper wire that can withstand 60/75 °C.

}

Ensure the EMC requirements of IEC 60204-1 are met.

}

The bus interface and input circuits of the safety control system/ the safety relay must
always be supplied by a single power supply.

}

The power supply must comply with the regulations for extra low voltages with protect-
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.

Preparing for operation

Supply voltage

AC

DC

A1

A2

L+

L-

Connection

Control via safety system

(PNOZmulti, PSS) or safety relay

(PNOZelog)

K1

Output 24 V DC

Input 24 V DC

A2

Y2

Y1

A1

24 V DC

0 V

PN

O

Z

p

o

w

e

r-B

u

s

Operation

NOTICE

The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.

Signal statuses of the inputs and outputs

}

K1: PNOZpower input circuit
– "1" signal (+24 VDC): Expansion modules are actuated

Содержание PNOZ pe2p

Страница 1: ...PNOZ pe2p Operating Manual 21035 EN 03 Safety relays...

Страница 2: ...umentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Interne...

Страница 3: ...e 5 Safety regulations 6 Use of qualified personnel 6 Warranty and liability 6 Disposal 6 Unit features 7 Block diagram terminal configuration 7 Function Description 7 Operating modes 7 Installation 8...

Страница 4: ...arly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measure...

Страница 5: ...put modules PNOZelog range units The bus interface may only be used in conjunction with units that evaluate a feedback loop The following is deemed improper use in particular Any component technical o...

Страница 6: ...with the basic regulations concerning health and safety accident preven tion Have read and understood the information provided in this description under Safety And have a good knowledge of the generi...

Страница 7: ...hen supply voltage is applied and the feedback loop Y1 Y2 is closed 24 V DC are available at the terminal K1 e g the PSS output has a high signal At the expansion module control output connected to th...

Страница 8: ...Zpower Layout The PNOZ pe2p is installed on the left of the first expansion module Maximum hardware 1 bus interface 6 expansion modules Expansion module 1 Expansion module 2 Expansion module 6 95579 T...

Страница 9: ...st always be supplied by a single power supply The power supply must comply with the regulations for extra low voltages with protect ive electrical separation SELV PELV in accordance with VDE 0100 Par...

Страница 10: ...oltage at Input circuit DC 24 V Feedback loop DC 24 V Current at Input circuit DC 30 mA Feedback loop DC 1 A Environmental data Climatic suitability EN 60068 2 78 Ambient temperature Temperature range...

Страница 11: ...p connectors or with TWIN crimp connectors 0 5 1 5 mm 28 14 AWG Torque setting with screw terminals 0 25 Nm Dimensions Height 29 mm Width 23 5 mm Depth 22 5 mm Weight 15 g Where standards are undated...

Страница 12: ...T p ThE SPIrIT Of SAfETY are registered and protected trademarks of Pilz Gmbh Co KG in some countries We would point out that product features may vary from the details stated in this document dependi...

Отзывы: