Commissioning
Operating Manual PNOZ mc7p
1003050EN02
13
6
Commissioning
6.1
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
}
Information given in the "Technical details" must be followed.
}
Use copper wiring with a temperature stability of 75°C.
}
Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
}
The power supply must meet the regulations for extra low voltages with protective sep
aration.
CAUTION!
Only connect and disconnect the expansion module when the supply
voltage is switched off.
NOTICE
When installing, you must refer to the guidelines of the CANopenUser
Group.
6.2
Interface assignment
It is possible to define which outputs on the safety system will communicate with CCLink.
The connection to CCLink is made via a 5pin screw connector.
1
2
3
4
5
DA
FG/
PE
DB DG SLD
DA
FG/PE
DB
DG
SLD
1: DA (Channel A)
2: DB (Channel B)
3: DG (Earth)
4: SLD (Cable shield)
5: FG/PE (Functional earth)