Function description

Operating Manual PNOZ m EF 8DI2DOT
1004649-EN-03

| 13

4.2.2

2-pole outputs

The expansion module provides two dual-pole outputs.

Features:

}

Signals at the output

– "0" signal (0 V) at the output (O+/O-):

Output is high impedance
No current to the load

– "1" signal (+24 V) at the output (O+/O-):

Output is low impedance
Current is supplied to the load

}

The max. capacity at an output depends on the load (see drawing on the max. capacitive
load). Connecting a higher capacity may lead to an error.

}

Operation with electronic contactors has not been tested and may lead to errors. Please
contact our Customer Support team if you are using electronic contactors.

}

Open circuit detection

}

Cannot be used as a single-pole output

Output tests

The following output tests are carried out:

}

Asymmetric test in error-free operation

– In this test, one output transistor is switched on and the other switched off for the test

duration t1 as a maximum. The load is not switched on because of the test. If errors
are detected during this test, then an advanced on test is run.

– The test duration t1 is max. 5 ms.
– The repetition time between the asymmetrical tests t2 is at least 30 s.
– The time t3 between two asymmetrical tests O+ and O- is at least 1 s.

}

Advanced on test in the event of an error

– The advanced on test is always run directly after an asymmetric test, in which an er-

ror has occurred. It is used to determine the cause of the error.

– The test is run for the test duration t1 as a maximum
– The test duration t1 is max. 5 ms.
– The test enables precise error diagnostics
– The load must not switch on because of the test.
– The following errors are detected:

Shorts across contacts (external error),
Short circuits and interruptions on the transistors,
Short circuits and open circuit on the connected load

Содержание PNOZ m EF 8DI2DOT

Страница 1: ...PNOZ m EF 8DI2DOT Operating Manual 1004649 EN 03 Configurable safe small controllers PNOZmulti 2...

Страница 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Страница 3: ...safety 11 4 Function description 12 4 1 Integrated protection mechanisms 12 4 2 Functions 12 4 2 1 Inputs 12 4 2 2 2 pole outputs 13 4 3 System reaction time 14 4 4 Block diagram 14 5 Installation 15...

Страница 4: ...Contents Operating Manual PNOZ m EF 8DI2DOT 1004649 EN 03 4 10 Order reference 27 10 1 Product 27 10 2 Accessories 27...

Страница 5: ...articularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive...

Страница 6: ...Introduction Operating Manual PNOZ m EF 8DI2DOT 1004649 EN 03 6 INFORMATION This gives advice on applications and provides information on special fea tures...

Страница 7: ...ing a press safety valve in accordance with EN 692 Open circuit detection configurable 8 inputs The inputs can be used to evaluate run monitoring for press applications Configurable pulse suppression...

Страница 8: ...OT 1004649 EN 03 8 2 3 Front view Legend X1 X3 Inputs I0 I7 X2 Dual pole outputs O0 O0 and O1 O1 X4 Supply connections 0 V 24 V Test pulse outputs T0 T1 LEDs POWER Run Diag Fault I Fault O Fault Termi...

Страница 9: ...programmable safety system should be installed in a protected environment that meets at least the requirements of pollution degree 2 Example Protected inside space or control cabinet with protection...

Страница 10: ...ork equipment devices systems plant and machinery in accordance with the general standards and guidelines for safety technology It is the company s responsibility only to employ personnel who Are fami...

Страница 11: ...nts are met This operating manual only describes the basic functions of the unit The expanded func tions are described in the PNOZmulti Configurator s online help Only use these functions once you hav...

Страница 12: ...n modules accordingly The online help on the PNOZmulti Configurator contains descriptions of the operating modes and all the functions of the PNOZmulti control system plus connection examples 4 2 1 In...

Страница 13: ...in error free operation In this test one output transistor is switched on and the other switched off for the test duration t1 as a maximum The load is not switched on because of the test If errors ar...

Страница 14: ...t1 of the expanded switch on test in case of a fault 4 3 System reaction time Calculation of the maximum reaction time between an input switching off and a linked out put in the system switching off i...

Страница 15: ...should be secured using a fixing ele ment e g retaining bracket or end angle Open the locking slide before lifting the unit from the mounting rail To comply with EMC requirements the mounting rail mu...

Страница 16: ...tted to the last expansion module Install the expansion module in the position configured in the PNOZmulti Configurator The position of the expansion modules is defined in the PNOZmulti Configurator T...

Страница 17: ...Configurator Use copper wiring with a temperature stability of 75 C Protect the supply voltage as follows Circuit breaker characteristic C 6 A or Blow out fuse slow 6 A The unit has two dual pole sem...

Страница 18: ...for the input circuit Input circuit Single channel Dual channel Example E STOP without detection of shorts across contacts S1 I0 L S1 I1 I0 L L Example E STOP with detection of shorts across contacts...

Страница 19: ...ct to the PNOZmulti system As soon as an additional expansion module has been connected to the system the project must be amended in the PNOZmulti Configurator and downloaded back into the base unit P...

Страница 20: ...ansion module is in a safe condition External error on the expansion module PNOZ m EF 8DI2DOT or on the overall system Expansion module is in a safe condition Faulty input signal at the expansion modu...

Страница 21: ...Operation Operating Manual PNOZ m EF 8DI2DOT 1004649 EN 03 21 Terminal LEDs Meaning T0 T1 Green Pulse output is used Pulse output is not used...

Страница 22: ...35 mA Power consumption 0 8 W Max power dissipation of module 8 W Status indicator LED Inputs Number 8 Input voltage in accordance with EN 61131 2 Type 1 24 V DC Input current at rated voltage 5 mA In...

Страница 23: ...0 EN 60068 2 78 Condensation during operation Not permitted Max operating height above sea level 2000 m EMC EN 61131 2 Vibration In accordance with the standard EN 60068 2 6 Frequency 10 55 Hz Acceler...

Страница 24: ...ection with screw terminals 1 core flexible 0 25 2 5 mm 24 12 AWG 2 core with the same cross section flexible without crimp connectors or with TWIN crimp connectors 0 2 2 5 mm 24 16 AWG Torque setting...

Страница 25: ...PL d Cat 2 SIL CL 2 2 10E 09 20 SC inputs 2 channel PL e Cat 4 SIL CL 3 4 27E 11 20 SC inputs Short circuit forming safety mats PL d Cat 3 SIL CL 2 1 80E 10 20 SC inputs 1 ch pulsed light barrier PL...

Страница 26: ...perating Manual PNOZ m EF 8DI2DOT 1004649 EN 03 26 9 Supplementary data 9 1 Maximum capacitive load C F with load current I A at the semiconductor outputs 500 1000 1500 2000 50 100 150 200 250 Capacit...

Страница 27: ...ule 8 inputs 2 dual pole outputs 772 144 10 2 Accessories Connection terminals Product type Features Order No Set spring terminals 1 set of spring loaded terminals 751 004 Set screw terminals 1 set of...

Страница 28: ...energy efficient products and environmentally friendly solutions We are represented internationally Please refer to our homepage www pilz com for further details or contact our headquarters Headquart...

Отзывы: