PSEN cs5.1 M12/8
Operating Manual PSEN cs5.1 M12/8
1003419-EN-06
26
Installation
CAUTION!
Potential loss of safety function due to changed device properties
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material.
– Please check the operating distances and the assured release dis-
tance.
}
The safety switch and actuator should be installed opposite each other in parallel.
Make sure that the actuator is aligned to the marking on the sensor that guarantees the
operating distance required by the plant design (see
}
Safety switches and actuators should only be secured using M4 screws with a flat head
(e.g. M4 cheese-head or pan head screws).
}
Torque setting: Please note the information provided under
}
The distance between two safety switches must be maintained (see
).
The distance can be undershot in certain application cases (see diagrams).
DEVICE
INPUT
SAFETY GATE
230
DEVICE
INPUT
SAFETY GATE
60
150
DEVICE
INPUT
SAFETY
GA
T
E
95
}
If using angled connector plugs, note the defined angle of the cable routing.
}
When installing make sure you comply with the requirements of EN ISO 14119.
}
Make sure that the safety switch and actuator cannot be used as an end stop.
}
For simpler installation, the mounting brackets (see
}
The actuator should be protected from unauthorised removal and from contamination.
Close the mounting holes using the seals provided (see diagrams). The use of seals
should be regarded as equivalent to using permanent fastenings in accordance with
Clause 7.2c of EN ISO 14119.