PSEN cs4.1n
Operating Manual PSEN cs4.1n
22180-EN-06
| 12
Wiring
Please note:
}
Information given in the "Technical details" must be followed.
}
Switch off the supply voltage before disconnecting the plug-in connection.
}
Make sure that when connecting or separating the connector the pollution degree 1 or 2
is maintained.
}
The power supply must meet the regulations for extra low voltages with protective elec-
trical separation (SELV, PELV).
}
The outputs of the safety switch must have a protective separation to voltages over 60 V
AC.
}
The supply voltage to the safety switch must be protected with a 2 A to 4 A quick-acting
fuse.
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
Pin assignment, connector and cable
1
2
3
5
4
5-pin M12 male connector
PIN
Pin
designation
Function
Wire colour
1
A1
+24 UB
Brown
2
12
Output, channel1
White
3
A2
0 V UB
Blue
4
22
Output, channel2
Black
5
-
Do not connect
Grey
The wire colour also applies for the cable available from Pilz as an accessory.