PSEN ma2.1p-34
Operating Manual PSEN ma2.1p-34
22192-EN-07
| 10
Wiring
}
Information given in the
Technical details [
17]
must be followed.
}
Calculation of the max. cable length l
max
:
R
lmax
- R
i
R
l
/ km
I
max
=
R
lmax
= Max. overall cable resistance (see evaluation device's technical details)
Ri = Internal resistance sensor (see
Technical details [
17]
)
R
l
/ km = Cable resistance/km of the cable (see technical details cable)
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
Refer to the notes on wiring in EN 60079-14.
}
Depending on which evaluation device is used, the overall cable resistance must be
checked; before commissioning it may also be necessary to check the cross circuit detec-
tion function.
}
Ensure that the safety switch's electrical connections cannot work loose.
}
Protect the safety switch's electrical connections from corrosion.
}
The safety contacts are not short circuit-proof.
}
UL requirement: the supply voltage must be provided via a Class 2 power supply.
WARNING!
Ignition in a potentially explosive area!
Unintentionally removing the connector while voltage is applied may trigger
an explosion, causing serious injury and death.
– Switch off the supply voltage before removing the connector.
– Protect the connector from being removed unintentionally.
Pin assignment
NOTICE
The colour marking for the connection lead only applies for the cable that
Pilz supplies as an accessory
The safety switch is shown in an unoperated condition.
Assignment of the 4-pin connector
[1]
[2]
[3+]
[4]
white
brown
blue
black