Wiring
Operating Manual PSSu E S 2DO 2(-T)
21352-EN-07
| 20
21
11
[1]
[3]
[2]
[4]
[5]
[6]
Please note:
}
The minimum cable cross section for field connection terminals on the base modules is
0.14 mm
2
(AWG26).
}
The maximum cable cross section for field connection terminals is:
– Digital inputs: 1.5 mm
2
(AWG16)
– Digital outputs: 2.0 mm
2
(AWG14)
– Inputs/outputs on the counter modules: 1.5 mm
2
(AWG16)
– Analogue inputs/outputs: 1.5 mm
2
(AWG16)
– Communication cables: 1.5 mm
2
(AWG16)
– Test pulse outputs: 1.5 mm
2
(AWG16)
– Power supply: 2.5 mm
2
(AWG12)
– Functional earth: 2.5 mm
2
(AWG12)