TECHNICAL MANUAL MT103
35
5.5
COMMISSIONING THE REGULATOR PLUS REFLUX 819 IN-LINE MONITOR WITH SB/82 SLAM-
SHUT VALVE (FIG. 24)
If there is also a relief valve in the line, refer to par. 3.1 to check it.
Check and adjust the intervention of the slam-shut 7 as follows:
A) For slam-shuts connected to the downstream piping by a three-way deviator push valve 11, proceed as follows
(fig. 21):
- connect a controlled auxiliary pressure to C;
- stabilise this pressure at the set-point established for the regulator;
- insert a reference pin 2 in the notch, pressing the knob 1 completely;
- reset the slam-shut device by means of the provided lever;
- keep the knob 1 pressed and:
•) for safety devices which intervention for maximum pressure: slowly increase the auxiliary pressure and
check the intervention value. If necessary, increase the intervention value by turning the adjustment ring
14 clockwise, or anticlockwise to reduce the intervention value.
•
) for safety devices for pressure increase and reduction: slowly increase the auxiliary pressure and record the
intervention value. Restore the pressure to the set-point established for the regulator, and carry out the
slam-shut reset operation. Check intervention for pressure reduction by slowly reducing the auxiliary
pressure. If necessary increase the intervention values for pressure increase or decrease by respectively
turning the rings 14 or 15 clockwise and vice versa to reduce the intervention values.
- check proper operation by repeating the operations at least 2-3 times.
B) On devices without the "push" valve (fig. 22) we recommend connecting the control head separately to a
controlled auxiliary pressure and repeat the operations described above.
ATTENTION
At the end of the operation, reconnect the control head to the downstream pressure take-off.
Fig. 24
| [email protected] | Phone: 877.566.3837 | Fax: 925.407.2903
Содержание REFLUX 819/FO
Страница 4: ...4 sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 8: ...8 sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 11: ...TECHNICAL MANUAL MT103 11 Fig 2A vent 204 A FO PILOT sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 45: ...TECHNICAL MANUAL MT103 45 204 A FO 205 A FO PILOT Fig 27 sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 46: ...TECHNICAL MANUAL MT103 46 PRE REGULATOR R14 A FO Fig 28 sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 52: ...TECHNICAL MANUAL MT103 52 VERSIONS Fig 29 A sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 66: ...66 TECHNICAL MANUAL MT103 10 0 LIST OF RECOMMENDED SPARES sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 72: ...72 TECHNICAL MANUAL MT103 PM 819 MONITOR DN 2 sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...
Страница 81: ...TECHNICAL MANUAL MT103 81 HB 97 SLAM SHUT DEVICE DN 4 sales mvandc com Phone 877 566 3837 Fax 925 407 2903 ...