TA466 Two-pole Voltage Detector

Copyright © 2020 Pico Technology Ltd. All rights reserved.

User’s Guide

3.5. Polarity check (direct voltage) 

• 

If the red test probe is connected to the positive terminal of the source, the   symbol is 

displayed.

• 

If the red test probe is connected to the negative terminal of the source, the   symbol is 

displayed.

3.6. Phase/neutral check (alternating voltages)

It is easy to spot neutral phases with the TA466. You perform this operation with the red test probe 

while holding the device. The black probe is not required and can be left clipped in place on the 

back the voltage detector  

If the red test probe comes in contact with a phase, the 

Phase 

symbol comes on (the display will 

turn blue). This provides an indication of contact with a phase only and is not an indication of safe 

working voltage at the contact point of the probe.

3.7. Phase order check (three-phase system on AC mains)

You can use the TA466 to determine the phase order in a three-phase system. You perform this 

operation in two sequences, using the two test probes. First, make sure that there is voltage 

present and that it has the same value for each of the three phases (at least 127 V).

Keep the red test probe in contact with phase 1 during the entire operation (Step 1 and Step 2).

Step 1:

•  Place the black test probe in contact with phase 2. 
•  The device is ready for the next sequence when the 

 symbol blinks.

Step 2:

• 

Move the black test probe to phase 3:

• 

If the symbol rotation is clockwise, the phase order is as well (L1, L2, L3).

• 

If the symbol rotation is counter-clockwise, the phase order is as well (L3, L2, L1).

• 

If the symbol disappears or keeps blinking, the three-phase system is not balanced.

Repeat the two steps to confirm the result.

Note 1: You only have 10 seconds to carry out Step 2.
Note 2: In the case of counter-clockwise order, we advise you to check the phase shift again by 

reversing the order of connections 2 and 3 to confirm the phase sequence.
Note 3: To start a new check (from Step 1 again), disconnect the device from the source you are 

checking and wait until the 

 symbol stops blinking.

Содержание TA466

Страница 1: ...User s guide TA466 Two pole voltage detector www picoauto com...

Страница 2: ...Battery level indicator 4 3 4 AC or DC voltage verification and measurement 4 3 5 Polarity check direct voltage 5 3 6 Phase neutral check alternating voltages 5 3 7 Phase order check three phase syst...

Страница 3: ...use on standard European outlets centre to centre distance 19 mm The voltage detector has the following features polarity indicator Audible continuity indicator 100 Phase order indicator in a three ph...

Страница 4: ...tative to arrange the return Note 2 The correct operation check function is there to make sure that the test leads battery and electronic circuit integrity are working and correct 3 3 Battery level in...

Страница 5: ...rmine the phase order in a three phase system You perform this operation in two sequences using the two test probes First make sure that there is voltage present and that it has the same value for eac...

Страница 6: ...test button 3 10 Battery replacement Make sure that the device is disconnected from all voltage sources The battery must be replaced when the correct operation check self test fails 1 Use a Pozidriv s...

Страница 7: ...bris and to recreate and or increase the insulation clean the device with a cloth coated with silicone MO984 Change the batteries Perform daily inspection Note For any non compliance during the period...

Страница 8: ...V AC 950 V DC Overvoltage protection CAT IV 600 V CAT III 1000 V relative to earth ground Indicators Audible alarm and light Display counts 1000 Input resistance 700 k at 50 V AC Frequency 50 60 Hz 3...

Отзывы: