3.4 Control Panel

3.4A Power Switch

The D385 has one control device, the power switch. When 

the power switch is moved to the “on” position your portable 

desiccant is dehumidifying. The machine will continue to 

dehumidify in all conditions until the power is turned off: 

There is no dehumidistat (see over-dry warning section 2.2).

3.4B Pilot Light

The power indicator lamp illuminates to indicate that the 

D385 is functioning properly. This indicator is helpful when 

a job site is too noisy to know what equipment is running 

properly. At a glance from across the room the operator can 

verify that the D385 is operating as it should.

3.4C Hour Meter

The hour meter will run whenever your D385 is on. This 

digital hour meter measures the cumulative time of 

operation in one-tenth hour increments. This non-resettable 

time is often used to verify hours on a job or to schedule 

maintenance. When the D385 is un-plugged the timer will 

continue to hold and display the cumulative hours run.

3.5 Location

Note the following precautions when locating the Phoenix 
D385:

•  It is designed to be used 

INDOORS ONLY.

•  If used on a water loss work site, plug it into 

GROUND 

FAULT CIRCUIT INTERRUPT (GFCI) OUTLETS

• 

DO NOT

 use the Phoenix D385 as a bench or table.

•  The air inlet on top and the side outlet must be at least 1 

foot from walls and other air flow obstructions.

•  If the humid area is very large, dehumidification can be 

improved by adding an outlet duct to circulate process air 

to stagnant areas.

3.6 Ducting Connections

Using excess duct length significantly reduces air flow volume 

through duct. This is true in any application. If the job at hand 

needs a short length of duct, cut a section to the appropriate 

length. If air flow is restricted by excess length, performance 

will suffer. The same can be said of excess bends in the 

ducting.
Three different duct sizes are used on the D385. All 

ducting materials are available from Therma-Stor LLC (see 

accessories list section 1).

Process in: 12” flex duct.

To attach flex duct to the process air intake, push the wire of 

the first couple of loops down below the four tabs in the top 

cover.

Process out: 10” diameter lay flat plastic duct. 

When inflated this ducting forms a 10” circle. 10” lay flat 

ducting attaches to the D385 by means of a 12”x 6” wire 

rectangle. To attach lay flat ducting to the process exhaust air 

(Fig. 1, P3), put the plastic duct end through the collar center 

and roll the plastic ducting’s end outward so that it overlaps 

the outside of the collar. The duct and collar quickly attach to 

the D385 by snapping over the four screw posts surrounding 

the process air exhaust (Fig. 1, P3).

Reactivation in & out: 6” flex duct.

Both reactivation air streams use the same type of duct 

connections.
The 6” flex ducting connections on the D385 consist of a 

detachable 6” starting collar. Slide 6” flex ducting over the 

starting collar and zip-tie or duct tape in place. To remove the 

starting collar (and its attached ducting length) depress the 

snap button and rotate the duct collar 15° clockwise. After 

rotating pull the duct collar straight out from the cabinet. Flex 

duct and collar may be stored beneath top cover.

3.7 Ducting Options

3.8 Storage and Transportation

The Phoenix D385 can be transported and stored in either 

upright or horizontal positions.
There is a storage compartment under the top cover of your 

dehumidifier. This compartment is large enough to store 

reactivation collars, power cords, filter (as used), as well as 

additional small items that you may require on your job site.

4 Maintenance

4.1 Air Filter Replacement

The Phoenix D385 is equipped with two pleated fabric air 

filters that must be checked regularly.

Process air stream filter:

This 16”x20”x2” filter is located in the top of your D385 

underneath the top cover. The stock filter supplied carries 

a MERV-11 filtration efficiency rating. This filter prevents 

loading the desiccant wheel with foreign matter.

PROCESS INLET

REACTIVATION INLET

NEGATIVE 
PRESSURE The 
Standard Setup 

If the D385 is in the 

drying chamber, air is 

being pulled into the 

chamber to compensate 

for the negative pressure 

created by the 

75 CFM

 

of reactivation air being 

ducted out.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

NEUTRAL 
PRESSURE 

The reactivation inlet and 

outlet are ducted from 

outside the drying area.  

This can be beneficial if 

the air outside the drying 

chamber is very damp.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

REACTIVATION INLET

Duct in from outside the 

affected area

POSITIVE  
PRESSURE 

The process inlet is ducted 

in from outside the drying 

chamber.  This can be 

beneficial if the outside air 

is dry.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

REACTIVATION INLET

Duct in from outside the 

affected area

PROCESS INLET

Duct some or all 

air from outside 

affected area

P/N 4037582

IDENTIFYING INLETS AND OUTLETS

PROCESS AIR 
STREAM

•  Air is pulled 

into the inlet

•  Humidity is 

adsorbed by 

the desiccant 

wheel

•  Dry air blows 

from the 

outlet

REACTIVATION OUTLET

PROCESS OUTLET

REACTIVATION AIR 
STREAM

•  Air is pulled into the 

inlet

•  It is heated to drive 

moisture out of the 

desiccant wheel

•  Hot moist air exhausts 

from the outlet

NOTE: LIQUID WATER 

MAY CONDENSE IN THE 

REACTIVATION OUTLET 

DUCT. SLOPE THE DUCT 

DOWNWARD TO PREVENT 

DAMAGE TO THE UNIT. 

MINIMIZE THE DUCT 

LENGTH AND USE THE 

STRAIGHTEST PATH 

POSSIBLE.

Refer to owner’s manual for additional setup information

Scan for more 

information on 

the D385

PROCESS INLET

REACTIVATION INLET

NEGATIVE 
PRESSURE The 
Standard Setup 

If the D385 is in the 

drying chamber, air is 

being pulled into the 

chamber to compensate 

for the negative pressure 

created by the 

75 CFM

 

of reactivation air being 

ducted out.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

NEUTRAL 
PRESSURE 

The reactivation inlet and 

outlet are ducted from 

outside the drying area.  

This can be beneficial if 

the air outside the drying 

chamber is very damp.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

REACTIVATION INLET

Duct in from outside the 

affected area

POSITIVE  
PRESSURE 

The process inlet is ducted 

in from outside the drying 

chamber.  This can be 

beneficial if the outside air 

is dry.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

REACTIVATION INLET

Duct in from outside the 

affected area

PROCESS INLET

Duct some or all 

air from outside 

affected area

P/N 4037582

IDENTIFYING INLETS AND OUTLETS

PROCESS AIR 
STREAM

•  Air is pulled 

into the inlet

•  Humidity is 

adsorbed by 

the desiccant 

wheel

•  Dry air blows 

from the 

outlet

REACTIVATION OUTLET

PROCESS OUTLET

REACTIVATION AIR 
STREAM

•  Air is pulled into the 

inlet

•  It is heated to drive 

moisture out of the 

desiccant wheel

•  Hot moist air exhausts 

from the outlet

NOTE: LIQUID WATER 

MAY CONDENSE IN THE 

REACTIVATION OUTLET 

DUCT. SLOPE THE DUCT 

DOWNWARD TO PREVENT 

DAMAGE TO THE UNIT. 

MINIMIZE THE DUCT 

LENGTH AND USE THE 

STRAIGHTEST PATH 

POSSIBLE.

Refer to owner’s manual for additional setup information

Scan for more 

information on 

the D385

PROCESS INLET

REACTIVATION INLET

NEGATIVE 
PRESSURE The 
Standard Setup 

If the D385 is in the 

drying chamber, air is 

being pulled into the 

chamber to compensate 

for the negative pressure 

created by the 

75 CFM

 

of reactivation air being 

ducted out.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

NEUTRAL 
PRESSURE 

The reactivation inlet and 

outlet are ducted from 

outside the drying area.  

This can be beneficial if 

the air outside the drying 

chamber is very damp.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

REACTIVATION INLET

Duct in from outside the 

affected area

POSITIVE  
PRESSURE 

The process inlet is ducted 

in from outside the drying 

chamber.  This can be 

beneficial if the outside air 

is dry.

REACTIVATION OUTLET

Must always be ducted out 

of the affected area

REACTIVATION INLET

Duct in from outside the 

affected area

PROCESS INLET

Duct some or all 

air from outside 

affected area

P/N 4037582

IDENTIFYING INLETS AND OUTLETS

PROCESS AIR 
STREAM

•  Air is pulled 

into the inlet

•  Humidity is 

adsorbed by 

the desiccant 

wheel

•  Dry air blows 

from the 

outlet

REACTIVATION OUTLET

PROCESS OUTLET

REACTIVATION AIR 
STREAM

•  Air is pulled into the 

inlet

•  It is heated to drive 

moisture out of the 

desiccant wheel

•  Hot moist air exhausts 

from the outlet

NOTE: LIQUID WATER 

MAY CONDENSE IN THE 

REACTIVATION OUTLET 

DUCT. SLOPE THE DUCT 

DOWNWARD TO PREVENT 

DAMAGE TO THE UNIT. 

MINIMIZE THE DUCT 

LENGTH AND USE THE 

STRAIGHTEST PATH 

POSSIBLE.

Refer to owner’s manual for additional setup information

Scan for more 

information on 

the D385

Содержание D385

Страница 1: ...ly or horizontally the D385 will fit inside most crawlspaces Having the D385 securely inside rather than outside the crawlspace access deters the possibility of tampering with the dehumidifier or the set up The 385 CFM of process air will provide 3 ACH on an affected area up to 7000 cubic feet The Phoenix D385 is easy to transport and set up The D385 will fit on your truck in the areas already des...

Страница 2: ...4022537 10 Lay Flat Duct 500 4024935 10 Lay Flat Duct 250 4024440 Kestrel 3000 Multi Function Air Meter Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix D385 dehumidifier Table of Contents Introduction 1 1 Safety Precautions 2 2 Specifications 2 3 Operation 3 3 1 How The ...

Страница 3: ...int liquid water will condense inside the duct work creating puddles If the reactivation exhaust air stream is not exhausted completely from the structure it can also cause secondary water damage Your Phoenix D385 does not produce liquid water internal to the machine There is no condensate pump and no drain hose The D385 desiccant dehumidifier will continue to remove water from already dry cold ai...

Страница 4: ...CTIVATION OUTLET Must always be ducted out of the affected area NEUTRAL PRESSURE The reactivation inlet and outlet are ducted from outside the drying area This can be beneficial if the air outside the drying chamber is very damp REACTIVATION OUTLET Must always be ducted out of the affected area REACTIVATION INLET Duct in from outside the affected area POSITIVE PRESSURE The process inlet is ducted ...

Страница 5: ... 12 x12 x1 filter is located in the bottom of your D385 To change the reactivation air filter lay the D385 down in a horizontal position The filter access slot is located on the bottom of the machine Fig 4 Open retainment clip remove old filter and replace with fresh filter The stock filter supplied carries a MERV 7 filtration efficiency rating This filtration prevents plugging the heater or loadi...

Страница 6: ...not fixed to driveshaft Tighten or replace set screw 4 Rotor is obstructed from rotating Check bearings and confirm rotor turns freely 5 Defective gear motor Rotor motor and heater operating blower s not operating 1 Defective blower or blower capacitor 6 Wiring Diagram PROCESS BLOWER GRN 25 BLK 11 WHT 24 CORD 1 CORD 2 WHT WHT BLK BLK BLK BRN BLU 27 BLU BLU RED RED WHT 9 BLK 8 BLU 7 ORG 6 BLU BLK G...

Страница 7: ...ATION AIR 6 4037807 HEATER CORE PHX D385 7 4029266 TOP COVER DESICCANT 385 8 4026898 THERMAL OVERLOAD CUT OUT SWITCH PROCESS AIR 9 4035235 11 CAPACITOR RUN 8 MFD DRY REACTIVATION AIR 10 1970010 CONTROL RELAY SPST 110VAC COIL 25AMP CONTACTS 11 4026773 MOTOR DESICCANT WHEEL 12 4026795 BELT DRIVE PHOENIX DESICCANT 13 4026772 WHEEL DESICCANT 14 4021475 FILTER AIR 16 X 20 X 2 PROCESS AIR 15 4026194 SWI...

Страница 8: ...horized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC reasonable control Limitations and Exclusions If any Phoenix D385 Dehumidifier part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that t...

Отзывы: