Phoenix 200 MAX Скачать руководство пользователя страница 6

6

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

5.  Rotate the blower outlet toward you as you remove it. 

Use care to avoid hooking wiring, tubing or electrical 

components.

6.  Reassembling with the new blower in the above 

procedure reversed.

4.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external 

overload, run capacitor, but no start capacitor or relay (see 

Fig. 3).

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power 
must be present to perform some tests; these tests should 
be performed by a qualified service person.
                  

4.6A Checking Compressor Motor Circuits

Perform the following tests if the blower runs but the 

compressor does not with the power switch ON.
1.  Turn the power switch OFF and unplug the unit, remove 

top panel and the cabinet front (6 screws).

2.  Plug in the unit and turn the power switch ON. Use a 

voltmeter to check for 110 to 120 volts between (a) the 

relay terminal that the black wire from the compressor 

connects to and (b) the capacitor terminal with the 2 

white wires & blue wire connected. If voltage is present, 

go to step 3. If no voltage, the low pressure control or 

relay are open or there is a loose connection in the 

compressor circuit. Test each component for continuity; 

see the appropriate section if a defect is suspected.

3.  Turn the power switch OFF and unplug the unit, then 

disconnect the red and yellow wires from compressor 

terminals R & S. Using an ohmmeter, check continuity 

between the points listed below.

4.  Compressor terminals C and S: No continuity indicates 

an open start winding; the compressor must be replaced. 

Normal start winding resistance 3 to 7 ohms.

5.  Compressor terminals C and R: No continuity indicates 

an open run winding; the compressor must be replaced. 

Normal run winding resistance is .5 to 2 ohms.

6.  Compressor terminal C and overload terminal 1: No 

continuity indicates a defective overload lead.

7.  Overload terminals 1 and 3: If there is no continuity, the 

overload may be tripped; wait 10 minutes and try again. 

If there is still no continuity, it is defective and must be 

replaced.

8.  Compressor terminal C and compressor case: Continuity 

indicates a grounded motor; the compressor must be 

replaced.

9.  Disconnect the wires from the capacitor. Set the 

ohmmeter to the Rx1 scale; the capacitor is shorted and 

must be replaced if continuity exists across its terminals. 

If there is no needle movement with the meter set on 

the Rx100000 scale, the capacitor is open and must be 

replaced.

10.  Reconnect the wires to the compressor and capacitor; 

plug in and turn on the unit. If the compressor fails to 

start, replace the run capacitor.

11.  If the unit still does not start, adding a hard-start kit will 

provide greater starting torque. If this does not work, the 

compressor has an internal mechanical defect and must 

be replaced.

4.6B Replacing a Burned Out Compressor

The refrigerant and oil mixture in a compressor is chemically 

very stable under normal operating conditions. However, 

when an electrical short occurs in the compressor motor, 

the resulting high temperature arc causes a portion of the 

refrigerant oil mixture to break down into carbonaceous 

sludge, a very corrosive acid, and water. These contaminants 

must be carefully removed otherwise even small residues will 

attack replacement compressor motors and cause failures.
The following procedure is effective only if the system is 

monitored after replacing the compressor to insure that the 

clean up was complete.
1.  This procedure assumes that the previously listed 

compressor motor circuit tests revealed a shorted or 

open winding. If so, cautiously smell the refrigerant from 

the compressor service port for the acid odor of a burn 

out. 

WARNING: The gas could be toxic and highly acidic. If no 
acid odor is present, skip down to the section on changing 
a non-burn out compressor.

2.  Remove and properly dispose of the system charge. DO 

NOT vent the refrigerant or allow it to contact your eyes 

or skin.

3.  Remove the burned out compressor. Use rubber gloves if 

there is any possibility of coming in contact with the oil or 

sludge.

4.  To facilitate subsequent steps, determine the type of 

burn out that occurred. If the discharge line shows no 

evidence of sludge and the suction line is also clean 

or perhaps has some light carbon deposits, the burn 

out occurred while the compressor was not rotating. 

Contaminants are therefore largely confined to the 

compressor housing. A single installation of liquid 

and suction line filter/driers will probably clean up the 

system.

 

If sludge is evident in the discharge line, it will likely be 

found in the suction line; this indicates the compressor 

burned out while running. Sludge and acid have been 

pumped throughout the system. Several changes of the 

liquid and suction filter/driers will probably be necessary 

to cleanse the system.

Содержание 200 MAX

Страница 1: ...rying areas to much lower humidity levels than conventional dehumidifiers The Phoenix 200 MAX an improved version of the original Phoenix 200 is the culmination of over a decade of LGR manufacturing and design expertise The Phoenix 200 MAX LGR High Capacity Dehumidifier Improved water removal 16 gals day 128 pints AHAM 80ºF 60 30 gals day maximum Improved grain depression The driest air from an LG...

Страница 2: ... GROUND FAULT INTERRUPTER DO NOT use the Phoenix 200 MAX as a bench or table It must always be used in the upright position Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix 200 MAX dehumidifier Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transpor...

Страница 3: ...ditions until the switch is turned off there is no dehumidistat If the unit is going to run for more than 2 hours in an area below 50 F the defrost timer should be adjusted to improve performance see Sec 2 9 2 7 Pump Purge Switch This switch left of hour meter minimizes the water left in the condensate pump reservoir for moving or storage Pressing and holding the pump purge switch will cause the c...

Страница 4: ...a drain 2 Plug in the unit but do not turn it on 3 Remove the air filter Slowly pour a quart of the chemical through the heat exchanger 4 Hold in the pump purge switch to reduce the water level in the reservoir 5 Flush with water 4 Service CAUTION Servicing the Phoenix 200 MAX with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death ...

Страница 5: ...ive blower Sec 4 5 Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 2 9 4 7 4 Air filter dirty Sec 3 1 5 Defective defrost thermostat Sec 4 7 6 Low refrigerant charge Sec 4 4 7 Air leak such as loose front cover 8 Defective compressor Sec 4 6 9 Rest...

Страница 6: ... replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 scale the capacitor is open and must be replaced 10 Reconnect the wires to the compressor and capacitor plug in and turn on the unit If the compressor fails to start replace the run capacitor 11 If the unit still does not start adding a hard start kit will provide greater starting ...

Страница 7: ...ormation on the evaporator coil the thermostat opens The compressor is then cycled off and on by the defrost timer The blower will continue to run causing air to flow through the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle 4 8 Condensate Pump...

Страница 8: ... of 200 MAX 6 Wiring Diagram 5 Options and Accessories 4021475 16 x 20 x 2 Pleated Media 65 MERV 11 Standardl 4022489 4 Mini Pleat Media 95 MERV 14 Optional 4024750 12 x 25 Intake Flex Duct 4024935 10 x 250 Lay flat Duct 4026600 Phoenix Solution LGR Performance Amplifier 4026734 Phoenix Shield Kit ...

Страница 9: ...918 1 Instruction Label 15 4029508 1 Low Pressure Control 16 4021796 1 Pump Purge Switch Item Part No Qty Description 17 4021822 1 Power Switch 18 4029266 1 Top 19 1 Wheel Axle Assembly 4026304 2 Wheel 12 4027125 1 Axle 1284404 2 Cotter Pin 20 4024078 1 Wire Duct Collar Exhaust 21 4025043 1 Skid Panel Items listed below are not shown 22 4023649 1 Condensate Pump 23 4028226 1 Condenser Coil 24 4024...

Страница 10: ...e for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC reasonable control Limitations and Exclusions If any Phoenix 200 MAX Dehumidifier part is repaired or replaced the new par...

Отзывы: