background image

6

www.usephoenix.com • [email protected]

Toll-Free 1-800-533-7533

Evaporator coil frosted continuously, low dehumidifying 
capacity.

.   Defrost thermostat loose or defective.
2.   Defrost timer incorrectly set or defective.
3.   Low refrigerant charge.
4.   Dirty air filter or air flow restricted.

Compressor runs with power switch OFF.

.   Defective relay.
2.   Defective power switch.

4.3 Blower Replacement

The motorized impeller has a PSC motor and internal 
thermal overload protection. If defective, the complete 
assembly must be replaced.
.   Unplug the power cord.
2.   Remove the top panel and cabinet front (6 screws).
3.   Disconnect the impeller leads.
4.   Remove four screws holding the impeller to the 

impeller brackets.

5.   Remove four screws holding the impeller brackets to 

the condenser shroud.

6.   Remove impeller and impeller brackets. Use care to 

avoid hooking wiring, tubing or electrical components.

7.   Reassemble with the new impeller in the above 

procedure reversed.

4.4 Defrost Thermostat and Timer

The defrost thermostat is attached to the refrigerant 
suction tube between the accumulator and compressor. 
If the low side refrigerant temperature drops due to 
excessive frost formation on the evaporator coil, the 
thermostat opens. The compressor is then cycled off and 
on by the defrost timer. The blower will continue to run, 
causing air to flow through the evaporator coil and melt the 
ice when the compressor is off. When the air temperature 
and/or humidity increase, the evaporator temperature 
will rise and the thermostat will close to end the defrost 
cycle. To improve performance in low temperatures refer to 
Section 3 for defrost timer adjustment.

4.5 Condensate Pump

Condensate is automatically pumped when the water level 
in the pump’s reservoir rises to close the float switch or if 
the pump purge switch is held in.
To replace the condensate pump:
.   Remove the metal strap holding the pump by loosening 

the 2 screws holding it in place.

2.   Disconnect the leads.
3.   Installation is the reverse of above, but check that 

the plastic inlet and outlet hoses do not rub against 
copper refrigerant tubes.

4.6 Gravity Drain Option

If the condensate pump fails and cannot be replaced 
immediately, the Phoenix 200 HT can be used by draining 
by gravity.
.   Unplug the unit and remove the front cover.
2.   Push the plastic plug on the left side out from inside 

the unit.

3.   Locate the heavy vinyl hose that connects the drain 

pan to the condensate pump. Pull the end out of the 
pump.

4.   Push that end of the vinyl hose through the hole in the 

left side.

5.   Connect a garden hose and run it to a drain. Keep 

the hose as flat to the floor as possible to avoid air 
pockets that would hinder draining. Placing the unit on 
something above the floor will also improve draining.

Figure 5: Defrost thermostat

Figure 6: Defrost timer

Figure 7: Condensate pump

Содержание 200 HT LGR

Страница 1: ...sier movement around the jobsite Recessed Condensate Hose Does not catch on obstructions and allows for dense storage setups by reducing overall width of the unit Patented Bypass Technology Increased Capacity The Phoenix 200 HT removes 5 more water than the 200 MAX Improved High Ambient Performance Patent pending technology allows superior efficiency in high ambient conditions Focused Airflow Pate...

Страница 2: ...t 80 F 60 RH If used in a wet area a ground fault interrupter GFI is required If an extension cord is required it must have a minimum of 14 gauge conductors if 25 feet long or less and 12 gauge conductors if greater than 25 feet long Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from yo...

Страница 3: ...fication This allows the condensate to be pumped 30 with the attached hose If the condensate must be pumped more than 20 feet above the unit a second pump must be added to relay the condensate If the pump fails and the unit must be used before it can be replaced the condensate can be drained by gravity The air inlet on top and the side outlet must be at least 1 foot from walls and other obstructio...

Страница 4: ...eral minutes it may cycle several times until the unit warms up 3 Maintenance 3 1 Air Filter The Phoenix 200 HT is equipped with a pleated fabric air filter that must be checked regularly The standard filter is a MERV 11 high efficiency filter Operating the unit with a dirty filter will reduce the dehumidifier s capacity and efficiency and may cause the compressor to cycle off and on unnecessarily...

Страница 5: ...witch defective 3 Loose connection in internal wiring No dehumidification neither blower nor compressor run with power switch ON and lit 1 Low pressure control open 2 Power switch defective 3 Loose connection in internal wiring Figure 4 Refrigeration system Some dehumidification blower runs continuously but compressor only runs sporadically 1 Unit is in defrost cycle 2 Defrost thermostat defective...

Страница 6: ...n causing air to flow through the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle To improve performance in low temperatures refer to Section 3 for defrost timer adjustment 4 5 Condensate Pump Condensate is automatically pumped when the water lev...

Страница 7: ...e compressor The contacts are closed when power is provided to the relay coil via the control circuit The control circuit includes the power switch low pressure control defrost thermostat and timer 5 Options and Accessories 4024682 Air Filter Pleated 2 x 16 x 20 57 MERV 8 4024750 Intake Flex Duct 12 x 25 Metalized Polyester 4024935 Lay Flat Duct 10 Round x 250 Roll 6 Wiring Diagram ...

Страница 8: ...16 Handle Assembly 1 4026094 Item Description Qty Part No 17 Pump Purge Switch 1 4021796 18 Hour Meter 1 4021597 19 Power Switch 1 4021822 20 Skid Plate 1 4025691 21 Instruction Label 1 4025723 22 Handle Screw M10 1 5 x 35 1 1177792 Handle Washer 1 4025517 Handle Nut M10 1 5 1 1223780 Items listed below are not shown Drain Hose 25 ID X 33 long 1 4024916 Front Panel Screw 1 4 20 X 1 2 1 1096006 Wir...

Страница 9: ...ing from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control Limitation and Exclusions If any Phoenix 200 HT Dehumidifier part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period appl...

Отзывы: