background image

Pro-series Ducted Evaporative Cooler Use and Care Manual    3

 INSTALLATION

CAUTION:

 

All electrical installations must comply with local 

and national building & safety codes; all work must be performed 
by qualified personnel only.

CAUTION:

 Disconnect all electrical power to the cooler before 

attempting to install, open, or service your cooler. If the cooler is 
thermostatically controlled, the thermostat must not be used as 
the power supply disconnect, as it may reset and start the unit 
unexpectedly.

CAUTION:

 If the cooler is supported by legs attached to each 

corner, the middle of the cabinet where the two sections join 
must be supported as well.

CAUTION:

 Do not screw or drill within 6 inches of the bottom of 

the wet section of the cooler, you could puncture the plastic 
water reservoir.

WARNING:

 Pump receptacles are for grounded evaporative 

cooler pumps only. Do not plug any other electrical equipment 
into the receptacles.

Even while routinely inspecting or servicing the inside, the cooler can 
be accidentally started. Keep all personnel away from the cooler and 
electrical supply when you are working on it. Before servicing or 
cleaning unit, switch power off at the service disconnects. Do not turn 
power to unit on until installation or service work is complete.

For maximum safety, make sure cooler cabinet, blower motor and 
pump are properly grounded to a suitable ground connection as 
required by all local and national codes.

Electrical Installation

THIS COOLER IS PRE-WIRED FOR 115 VOLT , 60 Hz POWER 
ONLY. 

NOTE: Improper voltage connections will void all warranties.

Mount Weatherproof Disconnect Switch Box

Located inside the parts box are the items required to mount the 
switch box to the cooler. Mount the switch box as follows:

1.

From inside of the cabinet (8), insert chase nipple (1) thru 7/8” hole 
and fasten it tightly to the cabinet with the conduit jam nut (2).

2.

Screw the switch box (3) onto the chase nipple (1) until tight and
box is aligned vertically.

3.

Insert the power supply wires from circuit board thru chase 
nipple into switch box.

Connect Power Supply

CAUTION:

 The external power supply to the unit must be 

adequately grounded and protected against overloads and short 
circuits per all national and local codes.

 

Run power supply to disconnect switch box and connect to the poles 
of the switch (4). Refer to the wiring diagram on the control box cover 
to complete the electrical installation of your cooler. Secure the switch 
into the box and install the gasket and switch cover (5).

 

Thermostat Cable Installation

The thermostat for this cooler is connected to the control panel by 
means of a thermostat cable (6 conductor minimum, not provided). 
Type CL2, 18 or 20 gauge, UL Listed thermostat wire is 
recommended.

1) Route one end of the thermostat cable (6) through the ½” hole in

the corner post on the left side of the access door and then through 
the ½” hole in the left end of the control box.

2) Insert the individual conductors of the thermostat cable (6) into the 

terminal block connections (9) on the left side of the printed circuit
board. Connect colored wires to terminals as follows: 

White to ‘C’

Brown to ‘H’

Red to ‘L’

Green to ‘P’

Yellow to ‘D’

Blue to ‘R’

Tighten screws carefully.

3) Install strain relief bushings (7) over the thermostat cable into the

½” holes in the corner post and control box, allowing a slight
amount of slack - do not stretch the thermostat cable tight. Replace 
the control box cover and tighten the 4 screws.

4) Select a location for the thermostat:

l

Mount the thermostat about 5 to 6   feet above the floor.

l

Mount the thermostat on an interior wall, not on an outside wall.

l

Do not mount near sources of heat or in direct sunlight.

l

Do not mount in the direct draft from cooler air registers.

l

Avoid dead air spaces which have little air circulation.

5) Install the thermostat using the “Mounting Instructions for

Thermostat” furnished with the cooler. 

7

7

4

4

6

6

5

5

3

3

2

2

1

1

9

9

8

8

1) Chase Nipple

2) Jam Nut

3) Junction Box

4) Disconnect Switch

5)Junction Box Cover

6) Thermostat Cable

7) Strain Relief Bushings

8) Cooler Cabinet

9) Terminal Block for Thermostat Cable

Содержание Aerocool Pro Series

Страница 1: ...to unit before working on or servicing cooler More than one disconnect switch may be required to de energize the equipment for servicing Do not remove access panels while cooler is running this may ca...

Страница 2: ...roduced by the cooler You can adjust different windows in the house to direct the most airflow to the areas that are occupied during different times of the day or night example living room windows dur...

Страница 3: ...ligned vertically 3 Insert the power supply wires from circuit board thru chase nipple into switch box Connect Power Supply CAUTION The external power supply to the unit must be adequately grounded an...

Страница 4: ...city and motor amperage may decrease due to the increased duct resistance The adjustable motor pulley is to be used ONLY to return the cooler motor to it s maximum allowable amperage and should not be...

Страница 5: ...uality etc For maximum cooling efficiency long life and appearance every two months during operation the cooler should be inspected and cleaned NOTE Do Not Undercoat the Water Reservoir The parts of y...

Страница 6: ...ore attempting to install open or service your cooler If the cooler is thermostatically controlled the thermostat is not to be used as the power supply disconnect as it may reset and start the unit un...

Страница 7: ...cci n de Instalaci n e Inicio es especialmente para el instalador La secci n segunda Mantenimiento contiene instrucciones de operaci n y mantenimiento paraelpropietario mientrasquelasecci ndeDetecci n...

Страница 8: ...vapores pueden ser inducidos por la unidad NOTA Cuando los enfriadores son instalados dentro de la jurisdicci n de los c digos de edificaci n de la Ciudad de Los ngeles solamente pueden ser instalados...

Страница 9: ...ra montar la caja del interruptor al enfriador Monte la caja del interruptor como sigue 3 Inserte los alambres de la fuente de poder de la tableta de circuito atrav s del niple hacia la caja del inter...

Страница 10: ...agua filtros gabinete etc P Filtros del enfriador se mojen parejos no reas secas P El ajuste del nivel del agua sea correcto P Verifique el flujo de agua completo P Turbina motor giran libremente no r...

Страница 11: ...s enfriador El enfriador debe recibir servicio completo a menos una vez por a o y m s seguido si las condiciones lo requieren ambiente polvo uso constante calidad del agua etc Para m xima eficiencia d...

Страница 12: ...brado no funciona Agua hacia el enfriador cerrada Corriente el ctrica desconectada Banda muy floja o apretada Motor no funciona Control termostato no funciona Banda rota Baja voltaje Banda demasiado a...

Отзывы: