QUINT-PS/24DC/24DC/ 5/CO

105537_en_02

PHOENIX CONTACT

11 / 22

9

Dimensions and mounting 

positions

Figure 4

Dimensions, keepout areas, and mounting positions

Possible mounting positions:

Normal mounting position, installation depth 125 mm (+ DIN rail) (delivery state)

Rotated mounting position, 270° Y-axis, installation depth: 35 mm (+ DIN rail)

QUINT PO

WER

+

-

Input DC 24V

Output DC 24V 5A

DC >

IN

DC

OK

Ι<

Ι

N

DC OK

Boost

18-29.5 V

19.2V

U <19.2 V

IN

+ +

- -

-

!

32

5

5

130

122

50

115

230

The required keepout areas for mounting vary depending on the application and ambient conditions. The 

keepout area dimensions specified in the figure are designed for the following application (nominal output 

power) and ambient conditions (ambient temperature):

Nominal output power:

 ≥

50

 

 

100%

Ambient temperature: -25 °C

 

...

 ≤

40 °C

For other variants, please refer to the table below.

Output power

Ambient temperature

Spacing [mm]

lateral

top/bottom

0

 

...

 

50

 

%

-25

 

...

 

70

 

°C

0

40

 

/

 

20

50

 

...

 

100

 

%

-25

 

...

 ≤

40

 

°C

5

50

100

 

...

 

125

 

%

15

50

 

...

 

100

 

%

>40

 

...

 

70

 

°C

Содержание QUINT-PS/24DC/24DC/5/CO

Страница 1: ...ng visualizes critical operating states and indicates them to the controller before errors can occur The application fields for DC DC converters are numerous Changing the voltage level Refreshing the...

Страница 2: ...ry side 12 12 Output 13 12 1 Protection of the secondary side 13 13 Output characteristic curve 13 14 SFB technology 14 14 1 Circuit breaker tripping characteristics 14 14 2 Installation notes 14 14 3...

Страница 3: ...itoring functions input 24 V DC output 24 V DC 2 x 10 A or 1 x 20 A including mounted UTA 107 30 universal DIN rail adapter QUINT ORING 24DC 2X10 1X20 2320173 1 Universal DIN rail adapter UTA 107 30 2...

Страница 4: ...onstant capacity restricted Output current 5 A 25 C 60 C 6 25 A with POWER BOOST 25 C 40 C permanently UOUT 24 V DC 30 A SFB technology 12 ms Magnetic circuit breaker tripping B2 B4 C2 Active current...

Страница 5: ...uit resistant Status display LED UIN 19 2 V yellow UIN 19 2 V DC LED on General data Insulation voltage input output 1 5 kV type test 1 kV routine test MTBF IEC 61709 SN 29500 890000 h 40 C Normal mou...

Страница 6: ...C Ambient temperature storage transport 40 C 85 C Max permissible relative humidity operation 100 at 25 C non condensing Vibration operation 15 Hz amplitude 2 5 mm according to IEC 60068 2 6 15 Hz 15...

Страница 7: ...ts burst EN 61000 4 4 Input 2 kV Test Level 3 asymmetrical 2 kV Test Level 3 asymmetrical Output 2 kV Test Level 3 asymmetrical 2 kV Test Level 3 asymmetrical Signal 1 kV Test Level 3 asymmetrical 2 k...

Страница 8: ...interference voltage in acc with EN 55011 EN 55011 EN 55022 Class B area of application Industry and residential Emitted radio interference in acc with EN 55011 EN 55011 EN 55022 Class B area of appli...

Страница 9: ...sible to open or modify the device Do not repair the device yourself but replace it with an equivalent device Repairs may only be carried out by the manufacturer The manufacturer is not liable for dam...

Страница 10: ...11 Strain relief for connecting cables 12 DIN rail adapter 8 Installation Figure 3 Convection DC OK U 19 2V IN I IN QUINT POWER Input DC 24 V Output DC 24V 5A DC OK N DC OK Boost 18 29 5 V U IN 19 2...

Страница 11: ...IN DC OK N DC OK Boost 18 29 5 V 19 2V U 19 2 V IN 32 5 5 130 122 50 115 230 The required keepout areas for mounting vary depending on the application and ambient conditions The keepout area dimension...

Страница 12: ...crew connectors on the DC input screw connection The DC DC converter converts a DC voltage of 18 32 V into adjustable regulated and electrically isolated output voltage The DC DC converter requires an...

Страница 13: ...works with the POWER BOOST power reserve as shown in the U I characteristic curve in the figure At ambient temperatures 40 C IBOOST is permanently available It is also available at higher temperature...

Страница 14: ...deliver a corresponding current pulse to supply the DC DC converter For example this can be achieved by upstream connection of a QUINT SFB power supply see accessories or suitable battery capacity En...

Страница 15: ...20 C The internal resistances of the circuit breakers are considered In addition to short circuit current the relevant power supply unit supplies half of the nominal current for paths connected in pa...

Страница 16: ...e high to low The DC OK signal is decoupled from the power output This makes it impossible for devices connected in parallel to act as an external power supply 15 2 Active switching output I IN During...

Страница 17: ...utput current must be reduced by 2 5 per Kelvin increase in temperature The device does not switch off at ambient temperatures of 70 C or thermal overload The output capacity is reduced as far as nece...

Страница 18: ...rved The characteristic curve can be used to determine the maximal output power to be drawn for each ambient temperature for different mounting positions Normal mounting position Rotated mounting posi...

Страница 19: ...70 X axis QUINT POWER In p u t D C 2 4 V O u tp u t D C 2 4 V 5 A D C O K N D C O K B o o s t 1 8 2 9 5 V U IN 19 2V U 1 9 2 V IN Z X Y IN IBOOST 25 0 10 20 30 40 50 60 70 80 C A Z X Y QUINT POWER Inp...

Страница 20: ...position 90 Z axis Rotated mounting position 270 Z axis IN IBOOST 25 0 10 20 30 40 50 60 70 80 C A Z X Y Q U I N T P O W E R I n p u t D C 2 4 V Output DC 24 V 5A D C O K N D C O K B o o s t 1 8 2 9 5...

Страница 21: ...ve the same conductor cross section Depending on the system a protective circuit should be installed at each individual device output e g decoupling diode or DC fuse for parallel connection of more th...

Страница 22: ...N in the case of n parallel connected DC DC converters Parallel connection for increasing power is used when extending existing systems Parallel connection is recommended if the DC DC converter does n...

Отзывы: