A 2.1
NLC-050… Modbus map
Table A-2
Coils 0-9999; Function codes 01, 05, 15
Nanoline variable type
Nanoline
range
Modbus address range
ModScan32-only address
range (decimal)
Hexadecimal
Decimal
Outputs
0-31
0x0000-0x001F
0000-0031
0001-0032
Flags
0-63
0x1000-0x103F
4096-4159
4097-4160
System Status Flags
64-71
0x1040-0x1047
4160-4167
4161-4168
Ethernet Command/Status
Flags
72-103
0x1048-0x1067
4168-4199
4169-4200
Table A-3
Discrete inputs 10000-19999; Function code 02
Nanoline variable type
Nanoline
range
Modbus address range
ModScan32-only address
range (decimal)
Hexadecimal
Decimal
Inputs
0-31
0x0000-0x001F
0000-0031
0001-0032
Table A-4
Input register 30000-39999; Function code 04
Nanoline variable type
Nanoline
range
Modbus address range
ModScan32-only address
range (decimal)
Hexadecimal
Decimal
Analog Inputs
0-7
0x0000-0x0007
0000-0007
0001-0008
Table A-5
Holding registers 40000-49999; Function codes 03, 06, 16, 23
Nanoline variable type
*
Nanoline
range
Modbus address range
ModScan32-only address
range (decimal)
Hexadecimal
Decimal
Register
†
0-31
0x0000-0x003F
0000-0063
0001-0064
Timer/Counter Preset
0-31
0x2000-0x203F
8192-8255
8193-8256
Output Time Preset
0-31
0x3000-0x303F
12288-12351
12289-12352
Timer/Counter Accum
0-31
0x5000-0x503F
20480-20543
20481-20544
Output Time Accum
0-31
0x6000-0x603F
24576-24639
24577-24640
*
These variable types are 32-bit values in the Nanoline and, therefore, occupy two Modbus register addresses. The
byte order is Little-endian, first byte contains LSB (i.e., the low-order 16-bits of Nanoline Timer/Counter Preset 0
would occupy Modbus Request Address 0x2000 and the high-order 16-bits of Nanoline Timer/Counter Preset 0
would occupy Modbus Request Address 0x2001. Nanoline Timer/Counter Preset 1 would occupy Modbus Request
Addresses 0x2002 and 0x2003)
†
Multiple Modbus commands may be required to view the entire Modbus range.
Содержание Nanoline NLC-035-024D-04I-02QRD-05A
Страница 1: ...User manual Installing and using Nanoline controllers UM EN NLC...
Страница 8: ...Nanoline 4 PHOENIX CONTACT 2338_en_O...
Страница 38: ...Nanoline 34 PHOENIX CONTACT 2338_en_O...
Страница 54: ...Nanoline 50 PHOENIX CONTACT 2338_en_O...
Страница 66: ...Nanoline 62 PHOENIX CONTACT 2338_en_O...
Страница 94: ...Nanoline 90 PHOENIX CONTACT 2338_en_O...
Страница 126: ...Nanoline 122 PHOENIX CONTACT 2338_en_O...