2338_en_O
Figure 3-10
RS-485 cable
Cables will need to be field wired.
3.5.2
Configuration
To configure Nanoline to Nanoline communication, one controller must be set as the
master. The slave controller node number must be set to 1.
Figure 3-11
“Serial port” dialog box for Nanoline to Nanoline communication
On the Nanoline controller to be set as the master controller:
1.
Click the “Nanoline… Configuration” menu to open the “nanoLC Configuration” dialog
box. In the “Base Unit” group click the “Configure” button. In the resulting dialog box,
choose the appropriate NLC-MOD-RS232 or NLC-MOD-RS485 option module. Click
the “Configure” button in the “Communication Option Module” group.
2.
Click the “Enable Master” check box in the “Configure Serial Port” dialog box (see
2
3
4
TX+
TX–
RX+
2
3
4
TX+
TX-
RX+
5 RX-
5
RX–
Pin 1
RJ11
RJ11
Pin 1