IBS IL 24 BK-T/U

14

6291A

   

       

      

       

      

       

      

      

       

      

  

24 V Main Supply/24 V Segment Supply

Connection

Through power connector
For terminal point assignment see page 3

Connection method

Spring-clamp terminals

Recommended cable lengths

30 m (98.43 ft.), maximum; do not route cable 
through outdoor areas

Voltage continuation

Through potential routing

Special demands on the voltage supply

U

M

/U

S

 are electrically isolated from the bus 

terminal supply U

BK

 if they are supplied 

separately. This is only possible when using two 
separate power supply units.

Behavior if voltage dips and interrupts occur

Voltages (main and segment supply) that are 
transferred from the bus terminal to the potential 
jumpers follow the supply voltages without delay.

Nominal value

24 V DC

Tolerance

-15%/+20% (according to EN 61131-2)

Ripple

±5%

Permissible range

19.2 V to 30 V

Current carrying capacity

8 A, maximum

Safety measures

Surge voltage

Yes

Polarity reversal

Yes

Provide an external fuse for the 24 V area

This 24 V area must be fused externally. The power supply unit must be able to supply 4 
times the nominal current of the external fuse, to ensure that the fuse blows safely in the 
event of an error.

Содержание IBS IL 24 BK-T/U

Страница 1: ...V voltages for low level signals Electrical isolation of the remote bus segments Automatic configuration of the outgoing interface as remote bus interface or local bus interface Support of up to 15 co...

Страница 2: ...A 0 0 3 B A R C B K T U R D L D U L U S U M Des Color Meaning BA Green Bus active RC Green Remote bus cable check RD Yellow Outgoing remote bus switched off LD Yellow Local bus switched off UL Green...

Страница 3: ...1 DO1 Receive Green 2 1 DO1 Receive Yellow 1 2 DI1 Send Pink 2 2 DI1 Send Gray 1 3 F GND Reference potential Brown 2 3 Not used 1 4 2 4 Shield Shield potential is connected with a capacitor to functi...

Страница 4: ...potential jumper and the FE spring on the bottom of the housing Functional earth ground is only used to discharge interference Connector 4 Power Connector 1 1 2 1 24 V DC US 24 V segment supply The su...

Страница 5: ...may damage the terminal Observe the current carrying capacity The maximum total current of the potential jumpers UM and US is 8 A Ground the bus terminal Connect the bus terminal to functional earth...

Страница 6: ...densation may appear on the outside of the housing if for example the terminal is brought into a closed room from a vehicle Permissible air pressure operation 80 kPa to 106 kPa up to 2000 m 6562 ft ab...

Страница 7: ...fer depending on the individual module The permissible number of devices that can be connected depends on the specific station structure Functions Reconfiguration external If necessary you can connect...

Страница 8: ...le when using two separate power supply units Behavior if voltage dips and interrupts occur Voltages main and segment supply that are transferred from the bus terminal to the potential jumpers follow...

Страница 9: ...DC Tolerance 15 20 according to EN 61131 2 Ripple 5 Permissible range 19 2 V to 30 V Minimum current consumption at nominal voltage 0 10 A DC At no load operation i e incoming remote bus connected no...

Страница 10: ...ns Power Interfaces Nominal value 2 x 5 V DC Tolerance 5 Ripple 1 5 Maximum output current 2 x 0 15 A DC Safety measures None Communications Power Internal Nominal value 1 x 5 V DC Tolerance 5 Ripple...

Отзывы: