Appendix: F-Parameters and iParameters
7619_en_05
PHOENIX CONTACT
B Appendix: F-Parameters and iParameters
B 1
F-Parameters
The values indicated in italics in Table B-1 are preset by the system and cannot be mod-
ified manually.
Table B-1
Overview of the F-Parameters for the module
F-Parameter
Default value
Description
F_Source_
Address
automatic
The parameter uniquely identifies the PROFIsafe source address (controller address).
The address is assigned automatically.
F_Destination_
Address
automatic
PROFIsafe destination address (address of the safe device)
The address is assigned automatically. However, the value can be modified.
Make sure that the value set under F_Destination_Address and the value that you
have set via the 10-pos. DIP switch are the same.
Value range: 1 ... 1022
F_WD_Time
150
Monitoring time in the safety module
A valid current safety telegram must arrive from the safe controller within the monitor-
ing time. Otherwise, the safety module enters the safe state.
The selected monitoring time must be sufficiently high for telegram delays to be toler-
ated by the communication, but still ensure a sufficiently fast error response in the
event of an error (e.g., interruption in communication).
Value range: 1 ... 65534, in 1 ms increments
Unit: ms
F_SIL
SIL 3
Safety integrity (SIL according to IEC 61508) of the safety module
F_CRC_Length
3-byte CRC
This parameter transmits the length of the CRC2 code to be expected in the safety tele-
gram to the safe controller.
F_Block_ID
1
Parameter block type identification
1: the parameter block of the F-Parameters contains the F_iPar_CRC parameter.
F_Par_Version
1
Version number of the F-Parameter block
1: valid for V2 mode
F_iPar_CRC
0
CRC checksum via the iParameters
The value must be greater than 0.
When verifying the safety function, check whether the F_iPar_CRC parameter is
greater than 0 for all devices. If not, check the iParameters and the CRC checksum in
the iParameter and F-Parameter.
WARNING:
Safety functions up to SIL 3 can be achieved with the safety module. The
safety integrity level that can actually be achieved depends on the param-
eterization, the structure of the sensor, and the cable installation (see
Содержание IB IL 24 PSDO 8-PAC
Страница 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Страница 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Страница 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Страница 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Страница 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Страница 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Страница 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Страница 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Страница 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Страница 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...