2.3.2
Grounding
The grounding is performed - depending on the type of device - with a slip-on sleeve (noise-
less ground / functional earth ground) or a ring cable lug (protective ground).
1.
Strip approx. 5 mm (0.197") off the wires.
2.
Fit the stripped wires - depending on the type of device - with a slip-on sleeve or a ring
cable lug.
3.
Plug the slip-on sleeve on the flat tab or mount the ring cable lug with the nut to the
threaded bolt.
Figure 2-33
Noiseless ground / protective ground
NOTICE: Damage
A separate copper conductor must always be provided for the grounding. The conductor
must have a minimum cross-section of 1.5 mm² (16 AWG) and must be kept as short as
possible.
You must adhere to a maximum torque of 1 Nm at an protective grounding on the
threaded bolt.
Содержание 2400452
Страница 1: ...Touch Panels with TFT Display User manual...
Страница 12: ...TP 3XXXX GEN3 12 PHOENIX CONTACT 106358_en_02 2 2 1 2 TP 3057Q Figure 2 3 Front panel dimensions in mm 147 203...
Страница 14: ...TP 3XXXX GEN3 14 PHOENIX CONTACT 106358_en_02 2 2 1 4 TP 3070W Figure 2 5 Front panel dimensions in mm 203 147...
Страница 16: ...TP 3XXXX GEN3 16 PHOENIX CONTACT 106358_en_02 2 2 1 6 TP 3105S Figure 2 7 Front panel dimensions in mm 295 220...
Страница 18: ...TP 3XXXX GEN3 18 PHOENIX CONTACT 106358_en_02 2 2 1 8 TP 3120W Figure 2 9 Front panel dimensions in mm 330 225...
Страница 44: ...TP 3XXXX GEN3 44 PHOENIX CONTACT 106358_en_02...
Страница 46: ...TP 3XXXX GEN3 46 PHOENIX CONTACT 106358_en_02...
Страница 58: ...TP 3XXXX GEN3 58 PHOENIX CONTACT 106358_en_02...
Страница 72: ...TP 3XXXX GEN3 72 PHOENIX CONTACT 106358_en_02...