Mounting and connecting the hardware
107068_en_06
PHOENIX CONTACT
43 / 74
4.9
Power supply of the controller
4.9.1
Sizing of the power supply
Choose a power supply unit that is suitable for the currents in your application. The selection
depends on the maximum currents arising, as well as the type of supply (separate supply of
U
L
, U
M
, and U
S
or supply via a power supply unit).
Some electronically controlled power supplies have a fallback characteristic curve (see
). They are not suitable for operation with capacitive loads.
We recommend using a primary-switched power supply (without fallback characteristic
curve) from the QUINT POWER range to operate the controller (see the latest Phoenix Con
-
tact catalog).
A power supply without a fallback characteristic curve must be used for correct operation
of the controller (see
).
When you switch on the controller, an increased inrush current will occur briefly. The con
-
troller behaves like a capacitive load when it is switched on.
Figure 4
-
8
Overload range
with
fall-back characteristic
curve
Figure 4
-
9
Overload range
without
fall-back charac
-
teristic curve
24
U
OUT
[V]
I
OUT
[A]
6219C070
1,1 x I
N
2,4 x I
N
I
N
Overload range
with fallback
characteristic curve
6219 071
C
24
U
OUT
[ ]
V
I
OUT
[ ]
A
I
N
1,5 x I
N
Overload range
without fallback
characteristic curve