Connecting and wiring the hardware
110146_en_00
PHOENIX CONTACT
75 / 128
6 Connecting and wiring the hardware
6.1
Power supply
6.1.1
Sizing of the power supply
WARNING: Loss of electrical safety when using unsuitable power supplies
The controller is designed exclusively for operation with protective extra-low voltage
(PELV) in accordance with EN 60204-1. Only protective extra-low voltages in accor
-
dance with the listed standard may be used for the supply.
The following applies for a PROFINET network and the I/O devices used in it:
• Only use power supplies that meet EN 61204-1 and feature safe isolation and
PELV in accordance with EN 61010
-
2
-
201. They prevent short circuits between
the primary and secondary side.
• To ensure the correct operation of the controller, only use power supplies
without
a fall-back characteristic curve
).
Please note:
When the controller is switched on, an increased inrush current is temporarily trig
-
gered. The controller behaves like a capacitive load when it is switched on.
Electronically controlled power supplies
with
a fall-back characteristic curve (see
) are
not
suitable for operation with capacitive loads.
To ensure the correct operation of the controller, you must use an external fuse.
• Use an external fuse (5 A, slow-blow).
• Make sure the power supplies and the external fuse are compatible. The power
supplies must be able to temporarily provide the tripping current.
Figure 6
-
1
Overload range
with
fall-back characteristic
curve
Figure 6
-
2
Overload range
without
fall-back charac
-
teristic curve
24
U
OUT
[V]
I
OUT
[A]
1.1 x I
N
2.4 x I
N
I
N
Overload range
with fall-back
characteristic curve
24
U
OUT
[ ]
V
I
OUT
[ ]
A
I
N
1.5 x I
N
Overload range
without fall-back
characteristic curve