Description of the controller
110146_en_00
PHOENIX CONTACT
65 / 128
IP addresses
Each Ethernet interface can be reached via a physical IP address.
IP address assignment via DHCP is not supported.
In the delivery state, the preset IP addresses for Ethernet interfaces LAN1, LAN2, and
LAN3.1/3.2 are as follows:
– IP address at LAN1: 192.168.1.10
– IP address at LAN2: 192.168.2.10
– IP address at LAN3.1/LAN3.2: 192.168.3.10
“SingleMode” redundancy
status
If you are operating your application with just one RFC 4072R (“SingleMode” redundancy
status), the preset IP addresses are used as physical IP addresses at the respective Ether
-
net interface.
Please note:
If you later wish to operate your application with two RFC 4072R controllers, the pre
-
set IP addresses at LAN1, LAN2, and LAN3.1/LAN3.2 will be used as system IP ad
-
dresses. The physical IP addresses at the Ethernet interfaces will then be set
automatically, as described in the
section.
Redundancy operation
In redundancy operation, the preset IP addresses are used as the system IP address of the
respective Ethernet interface. The controller that manages the process (PRIMARY control
-
ler) can also be reached via the system IP address of the respective Ethernet interface.
You can
only configure the system IP addresses
of the Ethernet interfaces. The physical
IP addresses of the controllers at the respective interface are set automatically based on the
set system IP address.
Table 4
-
1
Contact assignment of the Ethernet interfaces depending on the transmis
-
sion rate
PIN
LAN1, LAN2, LAN3.1/LAN3.2:
LAN1, LAN2:
10Base-T (10 Mbps)
100Base-T (100 Mbps)
1000Base-T (1000 Mbps)
1
TD+
(Transmit data+)
TD+
(Transmit data+)
DA+
(Bidirectional)
2
TD-
(Transmit data-)
TD-
(Transmit data-)
DA-
(Bidirectional)
3
RD+
(Receive data+)
RD+
(Receive data+)
DB+
(Bidirectional)
4
Reserved
Reserved
DC+
(Bidirectional)
5
Reserved
Reserved
DC-
(Bidirectional)
6
RD-
(Receive data-)
RD-
(Receive data-)
DB-
(Bidirectional)
7
Reserved
Reserved
DD+
(Bidirectional)
8
Reserved
Reserved
DD-
(Bidirectional)
Содержание 1136419
Страница 1: ...User manual Installing and operating the RFC 4072R Remote Field Controller...
Страница 126: ...RFC 4072R 126 128 PHOENIX CONTACT 110146_en_00...