Phocos FR 50 Скачать руководство пользователя страница 5

Electronics Diagram 

 

or 7.5A fuse

 

Fuse 

A fuse is required in order to protect the wiring.  A 
standard automobile fuse is recommended and the 
fuse should be wired to the positive (“+”) side of the 
system close to the positive battery terminal.  For 
12V operation, use a 15A fuse, and for 24Voperation 
use a 7.5A fuse.  

 

Operating Voltage 

Fuse 

12V 15A 
24V 7.5A 

 

ATTENTION:

  If a longer connection cable is necessary, the cable cross section (or gauge) must be equal to or greater 

than the cable sizes recommended on the following table.  Be careful that the input voltage at the 
appliance does not drop below the cut-out voltage of the compressor. 

 

Cable Size  

 

12V 

Cable Length 

24V 

Cable Length 

Area AWG 

mm

Gauge m  ft. m ft. 

2.5 


10 

12 
12 
10 

2.5 


10 

13 

19.5 
32.8 


12 
20 

16 
26 
39 

65.6 

 

Low Voltage Disconnect 

The compressor electronics includes a low voltage 
disconnect feature.  If the input voltage to the 
appliance falls below 9.6V (in 12 V mode) or 21.3V 
(in 24 V mode), the compressor will shut-off.  Once 
the voltage increases above 10.9V (in 12V mode) or 
22.6V (in 24V mode), the compressor will resume 
normal operation.   

This feature is designed to protect the system battery 
from experiencing too low a depth of discharge. 
 

 

12V Operation 

24V Operation 

Cut- in 

9.6V 21.3V 

Cut - out 

10.9V 22.7V 

 

 

 

 

Rev. 05/21/08 

5

Содержание FR 50

Страница 1: ...DC50 User s Guide 1 Rev May 21 2008 FR 50...

Страница 2: ...E LEFT OFF IN ITS NORMAL OPERATING POSITION FOR 2 HOURS PRIOR TO TURNING IT ON TO ALLOW THE COMPRESSOR OIL TO SETTLE IF THE APPLIANCE HAS BEEN HANDLED ON ITS SIDE OR STANDING ON END IT SHOULD BE ALLOW...

Страница 3: ...the cabinet Keep children away from the packaging material DANGER OF SUFFOCATION Installation This appliance is heavy Care should be taken when moving it This appliance operates on 12 or 24 Volts DC D...

Страница 4: ...r supports The floor must be sufficiently strong enough to support a fully loaded cabinet Use wood or metal shims to level the appliance if necessary Do not place the appliance close to heat sources h...

Страница 5: ...voltage at the appliance does not drop below the cut out voltage of the compressor Cable Size 12V Cable Length 24V Cable Length Area AWG mm2 Gauge m ft m ft 2 5 4 6 10 12 12 10 8 2 5 4 6 10 8 13 19 5...

Страница 6: ...function as it should The appliance will tend to run colder during these conditions and it may be necessary to turn the thermostat to a warmer setting towards the min If the room ambient temperature e...

Страница 7: ...the interior thoroughly Be sure to replace the plug on the defrost water drain 8 Reconnect the appliance to the electrical supply and leave running while empty for at least 2 hours allowing the inter...

Страница 8: ...due to Low Voltage Typically a connection is not as tight as it should be or the wire size to the compressor is too small The low voltage problem occurs at the instant of start up and is sometimes di...

Страница 9: ...NTY DOES NOT APPLY TO DAMAGE OR WEAR TO THE PRODUCT CAUSED BY ACCIDENT ABUSE MISUSE NEGLECT UNAUTHORIZED ALTERATION OR REPAIR OR IF THE PRODUCT WAS NOT INSTALLED IN ACCORDANCE WITH SUNDANZER PRINTED I...

Отзывы: