Product Guide - LRM1070, LRM1080

3

The OccuSwitch is designed for use in offices and 
similar applications, including toilets, storage rooms, 
etc. It is optimized for recessed ceiling mounting and 
for mounting heights between 2.5 and 3.5 meter.
The surface box allows surface-mounting as well, with 
either recessed wiring or surface-mounted ducts.
The advanced OccuSwitch can be connected in 
parallel (max 10) to cover larger area’s like open plan 
offices. The use of different mains groups or even 
phases is no problem.

The OccuSwitch’s detection pattern (see drawing) is  
4 by 5 meters for minor movements (desk work) and  
6 by 8 meters for major movements like walking.

Detection 

pattern          Position 

OccuSwitch

Standard application  

   Parallel operation

Functions (both versions)

Automatic control

The OccuSwitch switches the lights on automatically 
when movement is detected and switches the lights 
off after the area is vacated (after 1 to 30 minutes 
depending on the settings).

Daylight override

It is possible to prevent the automatic switch-on 
when sufficient daylight is available in order to create 
additional savings. 

Daylight switching

When daylight switching is active, the lights will 
automatically be switched off when sufficient daylight 
becomes available, and turned back on when the light 
level drops below the required level.

Functions advanced version

Parallel operation

It is possible to connect up to 10 OccuSwitches in 
parallel via a separate bus signal. When one of the 
OccuSwitches detects movement, all units will switch 
the lights on.  The bus signal is fully isolated, so each 
OccuSwitch can be used on any mains group or 
phase, allowing the use of several mains groups in an 
area and easy wiring. 

Local override

With a remote control it is possible to override the 
automatic operation of the OccuSwitch, for instance 
to switch lights off even if there is movement detected. 

Absence mode

When a remote control is used it is also possible to 
disable the automatic switch-on when people enter 
the area that the OccuSwitch is controlling.

Features (both versions)

Smart timer

The smart timer will extend the delay time by 10 
minutes if movement is detected shortly after switch-
off, assuming that the area is still in use, but very little 
movement is made.

Shield

The OccuSwitch has a retractable shield that can be 
used to shield off areas like corridors, adjacent to the 
area the OccuSwitch is controlling.

Features advanced version

Remote tool

With a remote control tool (IRT9090) it is possible to 
change the light level settings without the need to 
reach for the OccuSwitch itself.
Using the tool it is possible to change the power-up 
setting from its default (switch-on). The OccuSwitch 
will not switch on at power-up and will start detection 
30 seconds later.

Applications

8m

5m

6m

4m

4m

5m

5m

4m

5m

4m

Содержание OccuSwitch LRM1070/00

Страница 1: ...światło w pomieszczeniu lubna otwartej przestrzeni po opuszczeniu jej przez ostatnią osobę obniżając w ten sposób zużycie prądu nawet o 30 Przełącznik OccuSwitch może włączać instalacje pracujące na prądzie do 6 A oraz kontrolować pomieszczenia o powierzchni od 20 do 25 m2Złączka sieci zasilającej zapewnia łatwy montaż przełącznika OccuSwitch na suficieDostępny jest osobny przewód Wieland umożliwi...

Страница 2: ...MOV DET ST OccuSwitch 2018 Philips Lighting Holding B V Wszelkie prawa zastrzeżone Dane mogą ulec zmianie bez uprzedniego powiadomienia Znak towarowy jest własnością Philips Lighting Holding B V lub odpowiednich podmiotów www lighting philips com 2018 Maj 18 Dane wkrótce ulegną zmianie ...

Страница 3: ...Product guide OccuSwitch movement detector LRM1070 LRM1080 ...

Страница 4: ...tch in the ceiling A separate Wieland cable is available for easy fast and trouble free installation The OccuSwitch family exists of LRM1070 Basic OccuSwitch LRM1080 Advanced OccuSwitch LCC1070 Wieland cable LRH1070 Ceiling mounting box Dimensional drawing LRM1070 Basic OccuSwitch LRM1080 Advanced OccuSwitch LCC1070 Wieland cable LCC1070 Wieland cable LRH1070 Ceiling mounting box LRH1070 Ceiling m...

Страница 5: ...ow the required level Functions advanced version Parallel operation It is possible to connect up to 10 OccuSwitches in parallel via a separate bus signal When one of the OccuSwitches detects movement all units will switch the lights on The bus signal is fully isolated so each OccuSwitch can be used on any mains group or phase allowing the use of several mains groups in an area and easy wiring Loca...

Страница 6: ...ecting a location for the OccuSwitch avoid obvious cold spots so that condensation does not occur Fixing the OccuSwitch in a ceiling recessed Fixing the OccuSwitch on a ceiling surface mounted 80 82 mm 50 mm 30 mm 1 1 2 max 185 mm No 8 Ø 4 mm 35 Ø 95 mm 3 74 in 51 5 mm 2 03 in 56 66 mm 2 20 2 60 in 3 1 2 22 x 10 mm 25 x 13 mm 25 x 16 mm 16 x 16 mm LRH1070 LRM1070 LRM1080 3 1 2 4 5 22 x 10 mm 25 x ...

Страница 7: ...the OccuSwitch of being pushed out of the ceiling due to the weight of these ridged cables Parallel operation Parallel operation is used to enlarge the covering area of the OccuSwitch This can be done in two ways either by parallel installation or by using the parallel connection of the advanced OccuSwitch LRM1080 Parallel installation limits the total load to 6A and restricts the application to o...

Страница 8: ... 500 Lux required with 1000 Lux installed This will prevent the lights from switching on and off in a 15 minute cycle The OccuSwitch can switch off once or twice with a 15 minute delay for reference purposes This cycle will repeat every time the OccuSwitch is reconnected to the mains power Calibration Turn the dial to raise or lower the required light level Calibration Local control LRM1080 The Oc...

Страница 9: ... the power on and IR group settings together if changed To erase previous settings press reset followed by send on the IRT9090 B Warnings The OccuSwitch should not be used in the following situations In applications outside the specification range most notable heights above 3 5 meter Environmental conditions other than in a normal office environment temperature humidity In applications with heat s...

Страница 10: ...rew terminal CPF5 08 2VE or MSTB2 5 2 ST 5 08 Maximum wire range 1 5 to 2 5mm2 Maximum length 100m Settings LED indicator Red on movement detection Switch off delay 1 to 30 minutes Light levels 250 to 1000 Lux 30 reflection Detection range see diagram The remote control and light sensor work in a similar range Compliances and approvals Standards EN IEC 60669 2 1 Electronic switches Classification ...

Страница 11: ... 0 07 LRH1070 Outer box 400 x 300 x 300 42 cardboard 1 8 2 4 LCC1070 Unit box 90 x 90 x 90 1 plastic bag 0 13 0 17 LCC1070 Outer box 289 x 214 x 178 18 cardboard 2 4 2 7 Type MOQ Ordering number EAN code level 1 EAN code level 3 EOC LRM1070 00 OccuSwitch basic 1 9137 003 27803 8711559 731384 8711559 731391 731384 99 LRM1080 00 OccuSwitch advanced 1 9137 003 27903 8711559 731407 8711559 731414 7314...

Страница 12: ...g Holding B V all rights reserved Specifications are subject to change without notice Trademarks are the property of Philips Lighting Holding B V or their respective owners 3222 636 33176 6 October 2016 www philips com controls ...

Отзывы: