HF-Ri TD 1 35/49/80 TL5 E+ 195-240V
This intelligent high-frequency electronic dimming ballast utilizes the
DALI or Touch and Dim push-button protocol for fluorescent lamps.
It meets A1BAT requirements, thereby pre-empting upcoming
legislation. With a special command you can retrieve the system’s
mains power consumption, and with another you can find out which
lamp wattage is connected. Combined with controls, additional energy
savings can be achieved.
Product data
• General Characteristics
Interface
TD
Rated Number of
Lamps
1 piece
Rated Ballast-Lamp
Power
35/49/80
Rated Lamptype
TL5
Application code
E+
Line Voltage
195-240 V
Line Frequency
50/60 Hz
Housing
L 359x30x21
Ignition Method
Warm Start
Lifetime 90%
surv.@Tcaselife
50000 hr
Energy Efficiency
Index
A1 BAT
• Operating Characteristics
Automatic restart
Yes
Battery voltage
running lamps
176-254
Battery voltage lamp
ignition
198-254 V
Control input
protection
Yes (Basic insulation)
Inrush current Peak
28 (max) A
Inrush current Width
0.25 ms
Max ballast on
MCB(16A type B)
18 x
Earth leakage current
0.5 (max) mA
Mains voltage safety
(AC)
-10%/+10%
Mains voltage
performance (AC)
-8%/+6%
Overvoltage protec-
tion 320Vac
48 hr
Overvoltage protec-
tion 350Vac
2 hr
PowerFactor 100%
output power
0.95 -
Power losses gear
4.5 W
Regulating level
power
1%-100%
Stable lamp operation
temp.
> 15°C
Standby power
consumption
0.25 (max) W
Ballast Lumen Factor
1 -
Crestfactor
1.7 (max) -
Ignition time
1 (max) s
Operating frequency
110 (max) kHz
Total Harmonic
Distortion EUR
10 %
Hum and Noise level
Inaudible
• Wiring Characteristics
Cable-Cap output-
wires to earth
200 (max) pF
Cable-Cap output-
wires mutual
200 (max) pF
Conn.type input
terminals
WAGO 251 universal connector
[Suitable for both automatic wiring
(ALF and ADS) and manual wiring]
Conn.type output
terminals
WAGO 251 universal connector
[Suitable for both automatic wiring
(ALF and ADS) and manual wiring]
Conn.type ctrl input
terminals
WAGO 251 universal connector
[Suitable for both automatic wiring
(ALF and ADS) and manual wiring]
Striplength
8.0-9.0 mm
Dual fixture Master/
Slave
Yes [Master/Slave operation possible]