Philips EasyAir SNS200 Скачать руководство пользователя страница 4

4 - 5

Quick Installation Guide - EasyAir office sensor advanced grouping SNS200

January 2018

Product Data

 

Operation and Configuration via Mobile App

EasyAir operates immediately upon installation and 
energization without further commissioning. If changes from 
default settings are desired, EasyAir can be configured via an 
app through NFC or IR embedded within the sensor.

Compliance to Radio Equipment Directive (RED)

The Directive ensures a single market for Radio and Telecom mu nica-
tion Terminal Equipment by setting harmonized standards for safety 
and health, electromagnetic compatibility and the efficient use of 
the radio spectrum. This applies to all products using the radio 
frequency spectrum. This device is compliant to the underlying 
harmonized standards which is verified by an independent Notified 
Body. Any changes or modifications not expressly approved by 
Philips could void the user’s authority to operate this equipment. 
This product is intended for commercial use only.

Electrical Information
Input Voltage 

Powered by SR driver low-voltage interface

Current Consumption 

13 mA

Nominal Power Consumption 

200 mW

Standby Power 

< 1 W on luminaire level, including driver standby power

Occupancy Sensing
Type 

Passive infrared (PIR)

Occupancy based control 

Default enabled

Occupancy Mode 

Auto-on/off, Manual-on/off, Manual-on/auto-off; Red LED indicates “on”

Group Occupancy Sharing 

Enabled/disabled

Group Light Behaviour

Background Light Level, Field Task Level

Hold Time 

0.5 - 60 minutes

Viewing Angle 

X = 72°, Y = 86° ( See detection pattern)

Background Light Level 

0-100%

Prolong Time 

0 minutes - infinity

Grace Fading 

0-25 sec

Response Time/Fading to Switch On/Off 

0.7 sec

Daylight Sensing
Daylight based control

Default enabled

Auto-calibration 

Upon power-up

Daylight dependent switching

Default disabled 

Daylight dependent override

Default disabled 

Viewing Angle 

40° (half value sensitivity); 2% cut-off point at 75°

Task Tuning
Full Light Setting 

0-100%

Environment & Approbation
Operating Ambient Temperature Range 

0 °C to 55 °C

Operating Humidity 

0 – 95% non condensing

Storage Temperature 

-25 °C to 85 °C

Storage Humidity 

0-95% non condensing

Max Case Temperature (Tcase) 

55 °C

Agency Approbations 

CE, ENEC, RTTE, EMC

Warranty 

5 years warranty for released Philips system combination (sensor and compatible driver).  
3 years warranty for sensor only.

Digital Interface 

Xitanium SR

Other
Status Indicators 

Red, Yellow. Yellow LED on: Vacancy & Sensor is functional; Red LED on: Motion is detected

Energy reporting

Calculated from last “power on”: % On, Energy Consumed (Whr), System on time (hrs), Avg power consumed 
(w-hr), Lamp on time (hrs)

No. Drivers per Sensor 

4 max

Max Distance Switch-to-First-Luminaire 

10 m line-of-sight

Max Distance Luminaire-to-Luminaire 

12 m line-of-sight

No. Switches per Group 

10 max

Field Configuration 

via NFC or IR, parameters set via Philips field apps

Содержание EasyAir SNS200

Страница 1: ...3 50 pcs EasyAir SNS200 g Grey Office Sensor Advanced Grouping 8718696 712412 00 929001 560 703 50 pcs Compatible LED Drivers Logistic code 12NC Description 929001516306 Xitanium 36W 0 3 1A 54V SR 230V 929001505006 Xitanium 75W 0 7 2 0A 54V SR 230V 929001540406 Xitanium 35W 0 08 0 35A 150 V SR 230V 929001540506 Xitanium 60W 0 08 0 35A 220 V SR 230V 929001540606 Xitanium 60W 0 08 0 35A 300 V SR 230...

Страница 2: ...ting Dimensions mm Mounting in U shaped slot in sheet metal max thickness 1 mm EasyAir office sensor Sensor Dimensions mm 43 8 MAX 16 8 MAX 7 5 MAX 24 3 MAX 50 0 MAX 2 3 43 5 43 5 16 0 16 0 Mounting in cut out in sheet metal thickness 0 7 mm to 1 2 mm 44 0 17 0 2 3 Mounting hole dimension 0 2mm ...

Страница 3: ...t Mounting in SMB 50 bracket All dimensions in mm Installing EasyAir office sensor with ceiling mount bracket SNS200CMP The ceiling mount bracket SNS200CMP is premounted with EasyAir SNS200 sensor and the cable See the cut out in ceiling and mounting dimensions below all in mm 74 Radius min 5 mm 74 86 Ø 63 Ø 74 Radius min 5 mm 74 46 86 Ø 63 Ø 74 Radius min 5 mm ...

Страница 4: ...f Manual on auto off Red LED indicates on Group Occupancy Sharing Enabled disabled Group Light Behaviour Background Light Level Field Task Level Hold Time 0 5 60 minutes Viewing Angle X 72 Y 86 See detection pattern Background Light Level 0 100 Prolong Time 0 minutes infinity Grace Fading 0 25 sec Response Time Fading to Switch On Off 0 7 sec Daylight Sensing Daylight based control Default enabled...

Страница 5: ...make changes in specifications and or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication 01 2018 Data subject to change www lighting philips co uk oem emea products connected lighting ...

Отзывы: