DMRC210-RJ-DA  

EcoSet Relay Controller 

 

 
Installation Instructions 

…………………………………………………....……………………………………………………
……

 

 

 

        

Connect Data Cable in a ‘Daisy Chain’ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial Cable Termination  

RJ12 connectors using flat cable recommended. 

Double-adaptor (Y-splitter) is usable for spurs. 

 

 

Electrical diagram 

 

 

RJ12

DyNet

RS485

RJ12

µP

DIPswitch

Supply:

230V 

1 Phase

20A

L

IN

N

CH1

out

CH2

out

N

isolation barrier 

(double-insulated)

 

 

Installation Overview 

 

  

WARNING

 

Before installation or servicing, 
disconnect power at circuit breakers or 
remove fuses to avoid electrical shock 
or damage to the unit. It is 
recommended that an electrician 
perform this installation.

 

To reduce the risk of fire or electric shock , do not expose this 
device to rain or moisture.   

Do not energise unless the front cover is in place. Network (DyNet) 
wiring is SELV and must be double 

– insulated from mains in 

accordance with the local wiring rules. Installation, programming 
and maintenance must be carried out by qualified personnel. 

No more than 60 DMRC210 units may be safely connected to a 
single Dynet network without additional grounding precautions. 

 