Philips Dynalite DDBC300-DALI Скачать руководство пользователя страница 2

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

product specifications 

connecting data cable 

Supply: 

 

100 

– 240V 50/60Hz Single Phase at 0.5A 

Control Output:

 

3 x DALI Control Outputs, each supporting a full DALI universe of 64 channels (192 total), including backward 
channel 

Supply Terminals:

 

Line, Neutral, Earth 1 x 4mm2 max conductor size 

DALI Terminals:

 

3 x Ballast DALI circuit - Dx, Dx - 1 x 4mm2 max conductor size 

Control Inputs:

 

1 x RS485 DyNet serial port 

 

1 x AUX programmable dry contact input 

DALI BUS DC Supply:

 

Integral 24V 250MA power supply 

DyNet DC Supply:

 

200mA (Supply for approx 10 panels) 

Preset Scenes:

 

170 

Compliance:

 

CE, C-Tick 

Operating Environment:

 

0° to 40°C ambient temperature  

 

0% to 90% RH non-condensing 

Construction:

 

Polycarbonate DIN rail mount 

Dimensions:

 

H 93mm x W 211mm x D 75mm 

Weight:

 

0.49kg 

 

DDBC300-DALI Instruction Manual Rev E Specifications subject to change without notice 

 Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921)  Unit 6, 691 Gardeners Road  Mascot  NSW  2020  Australia  Tel: +61 2 8338 9899 Fax: +61 2 8338 9333 

E-Mail: 

[email protected]

      Web: 

Philips.com/dynalite

      

 

 

installation steps 

1.  Mount the device on a DIN rail inside an approved enclosure. 
2.  Connect mains cables: Connect 

a 0.1A single phase supply to the Supply terminals, this will operate the product’s 

electronics.  This device must be earthed. 

3.  Connect the DALI bus cables: Use a mains rated 2 core cable to connect the DALI bus to the DALI ports on all DALI 

devices. The DALI bus cable should not be longer than 300 Metres, and should have a minimum cross section area 
based on cable length as follows: 
- Up to 100 Metres:   0.5mm

2

 

- 100 to 150 Metres: 0.75mm

2

 

- 150 to 300 Metres: 1.5mm

2

 

The DALI bus is not SELV and must be treated as a mains cable. It is not polarity conscious. A maximum of 64 DALI 
devices can be wired to each DALI port.  
 

4.  Connect data cables to the device as per diagrams below. Segregate data cables from mains cables. 
5.  If the Auxiliary input is to be used, connect a dry contact device in between the AUX and GND terminals. Keep cable 

runs between the AUX terminals and the dry contacts under two metres. The function of the Auxiliary input will need 
to be programmed at the time of commissioning. 