Philips DUS804C-UP Скачать руководство пользователя страница 2

instructions 

 

 

2   

DUS804C-UP Installation Manual Rev D.docx

 

pages. Note that the product has two functions, and the optimum mounting location for each individual function may 

conflict with each other, and may require use of multiple sensors. 

DUS804C NETWORK CONNECTIONS

 

Motion detection installation steps 

• 

An ultrasonic sensor should never be located within 17.5 meters of another ultrasonic sensor.    

• 

Chose a location where it may face doorways etc which could cause false triggering.  

• 

Position the sensor so it is between 2.1 and 4.0m from the floor. Optimum height is 2.4m 

• 

Position the sensor so it is at least 1m away from electrical lighting such as neon and fluorescent lights 

• 

Position the sensor as to avoid exposing it to direct sunlight. Sensor should be at least 2.5m from horizontal or 

vertical air ducts   

• 

Position the sensor where pedestrian traffic is likely to walk across the detection zones  

• 

Fix the sensor to a firm section of ceiling. Sensor can be surface mounted using ring provided. 

• 

Note that for the DUS804C-UP coverage area is rectangular (see Motion Detector coverage diagram)  

• 

When terminated and power there are three indicating LED‟s for the following information 

o

 

Blue

 = Low network voltage. The sensor must receive minimum of 12VDC from the Dynet network. If 

the  right  network  voltage  is  not  present  at the  sensor  terminals  when  the  whole  system is  powered, 

then additional network power supplies (DDNP1501) will be required. 

o

 

Green

 = Ultrasonic detection activity 

o

 

Red

 = PIR detection activity 

• When  terminated  correctly  and  powered  from the  Dynet  network the  sensors  LED‟s  will flash for  5 min  every time  a 
Dynet push button is pressed. This is  so the installer can confirm the sensor is terminated correctly with other network 

devices. 
• Only after all network devices are confirmed to be terminated correctly can the commissioning of the system begin.  

 

PIR sensor 

Network sign 
on button & IR 
window 

Ultrasonic 
sensors

 

Recommended Cable Types 

Belden:  

9503 

Garland: 

MCP3S 

Hartland: 

HCK603 

M&M Cable: 

B2003CS 

Dynalite: 

DYNET-STP-CABLE

 

STANDARD CABLE CONNECTION

 

Recommended Cable Colours 

Green/White Pair 

paralleled for GND 

Orange/White Pair 

paralleled for +VE 

Blue/White Pair  

Blue for DATA + 

 

 

 

White for DATA -

 

Light level sensor 

Indicating LED’s 

Содержание DUS804C-UP

Страница 1: ...noccupied for a certain amount of time lights can be automatically dimmed or switched off to provide energy savings The unit also incorporates a segmented click up bezel surrounding the motion sensor element This enables a portion of the sensing field to be readily masked to prevent nuisance detection from adjacent doorways or corridors The same sensor provides IR control reception to enable full ...

Страница 2: ...UP coverage area is rectangular see Motion Detector coverage diagram When terminated and power there are three indicating LED s for the following information o Blue Low network voltage The sensor must receive minimum of 12VDC from the Dynet network If the right network voltage is not present at the sensor terminals when the whole system is powered then additional network power supplies DDNP1501 wi...

Страница 3: ...ell mounting location Position the sensor so it sees a combination of artificial light and natural Light Position the sensor so it is not directly exposed to artificial light or sunlight For programming instructions refer to Dynalite Tech Note Setting up PE functions Lens pattern DUS804C UP Mounting Dimensions ...

Страница 4: ...ons and design subject to change without notice Philips Dynalite manufactured by WMGD Pty Ltd ABN 33 097 246 921 All rights reserved Dynalite Dimtek DyNet and DLight and associated logos are the registered trademarks of Dynalite Intelligent Light Pty Ltd Not to be reproduced without permission E Mail dynalite info philips com Web philips com dynalite DUS804C UP PIR Maximum detection range 5 0m Det...

Отзывы: