background image

Mounting Instructions

NOTE: First turn off electricity.

1. Remove mounting plate from fixture.

2. Knockout in back of mounting plate and push wires through 
    the hole.
3. Securely attach mounting plate to J-box.

Transformer Connect to PCB Ass'y

PCB  Ass'y

Mounting Plate

Transformer

6. Connect red lead to battery positive terminal.

Red Wire

Battery

7. Snap fixture onto mounting plate and ensure no wires are 

    pinched. Make sure unit is fully attached.

8. Restore power and press test button. Battery powered bulb

    will come on. AC light will turn off

5. Connect transformer to PCB Ass'y.

Pipe(Not provided)

Pipe Connector

Nut

Screw

Wall Mounting

Ceiling Mounting

1. Open top cover and knockout on the top of fixture.

2. Secure the mounting plate to tube with nut.

knockout

Junction Box

(Not provided)

BL

AC

K

WHITE

ORANGE

120VAC

 INPUT

277VAC
 INPUT

4.

ELECTRICAL CONNECTIONS:

    Connect white wire lead from fixture to white (neutral) wire supply 
    feed from circuit.  Connect  black (120V) or orange (277V)   
    (depending on supply voltage) wire lead from fixture to black(hot) 
    wire from supply circuit.Use U.L. Listed wire connectors suitable 
    for the size, type, and number of conductors. No loose strands or 
    loose wires should be present. Secure wire connectors with U.L 
    listed electrical tape

3. Reference 4 - 8 step in wall mounting above for ceiling 

    mounting.

Rev A 11/10 Page 1 of 2

Philips Day-Brite • 776 South Green Street • Tupelo, MS 38804

662-842-7212 • Fax 662-841-5501 • www.daybrite.com