Self Diagnostic System Operation –Emergency Light or EXIT Sign Products

Normal Power Up Sequence 
 
At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute 
a “Power Up Quick Test” causing the green LED indicator to flash rapidly. If any faults are detected during the “Power Up 
Quick Test” these will be evident by a flashing red LED indicator.  If the audible diagnostic option has been ordered, the 
flashing red LED will be accompanied by a simultaneous beeping tone. 

(Note: A continuous rapid alternating Red/Green 

flash with rapid beeping tone indicates 277V applied to 120V input lead. TURN OFF POWER IMMEDIATELY!) 

 
Emergency Operation 
Emergency operation occurs when AC power fails. The product remains in emergency operation until AC power is 
restored or battery capacity is depleted. During emergency operation both red and green LED indicators are disabled. 
 
User Interface 
 

Green LED indicator

 

 

Slow Flash/Continuous ON = AC power present; normal operating condition 

 

Rapid Flash = product performing an automatic or manually initiated diagnostic test 

Red LED indicator 

 

Single Flash = battery fault 

 

Two Flashes = lamp failure (light bar failure – EXIT signs) 

 

Three Flashes = charger fault 

 

Four Flashes = transfer fault 

(If more than one fault condition is present simultaneously, the red LED will flash the indication pattern for each 
fault independently then repeat the cycle.) 
 

Pushbutton Test Switch

 

 

Long Press (longer than 0.5sec) transfers product to emergency operation during time the button is 
pressed. 

 

Short Press initiates self diagnostic activities as follows: 

 

One Press cancels diagnostic test presently running. 

 

Two Presses starts a one minute diagnostic test. 

 

Three Presses starts a 90 minute diagnostic test. 

 

Four Presses conducts a lamp load calibration (emergency light products only). 

 

Seven Presses initiates a system reset. 

(Note: the microprocessor will allow up to seven, one minute diagnostic tests within the first 24 hours of 
operation. Allow 24 hours of charging before performing any long duration testing.) 
 

Buzzer

 (optional)– Sounds in unison with the flashing red LED if a fault condition is present. Buzzer may be 

silenced for up to 196 hours by a short press of either the test switch or the optional IR remote control device 
“silence” button. Correcting fault condition will cancel fault notification. Lamp failure indication requires a 
manually activated diagnostic test after lamp replacement to cancel notification. 
 

IR Remote Control 

(optional)- is a hand held device that allows remote activation of diagnostic testing and 

silencing of the optional buzzer during fault conditions. 

Содержание CMFIC Series

Страница 1: ...ecommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Do not use outdoors Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters CAUTION Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage protect lamp against abrasion and scratches and against l...

Страница 2: ...it charger leads Blue 277 VAC Black 120 VAC White Common Green Ground 1 Connect remote lamps if applicable to orange and yellow flying leads connected to RL and RL respectively Ensure total unit load including internal lamps does not exceed unit rating 2 Adjust head s to illuminate desired area s 3 Close cover and screw shut Ensure electrical wires and membrane switch cable remain inside unit and ...

Страница 3: ...ally initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec trans...

Страница 4: ...1 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053340 February 2016 OPTIONAL REMOTE CONTROL Front Press appropriate button to perform the indicated test or silence the audible alarm Cancel stops any test currently in process Back Explanation of indicator light flash sequences Refer to Table 2 above for further information ...

Страница 5: ...lips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053340 February 2016 BATTERY HOOKUP DIAGRAMS LEAD BATTERY HOOKUP 6V 25W LEAD 6V 50W LEAD 12V 50W LEAD NICAD BATTERY HOOKUP 6V 25W NICAD 6V 50W NICAD 12V 25W NICAD 12V 50W NICAD ...

Отзывы: